12
VB 230/400-25
12. Commissioning
:The device is to be put into opteration in 3 steps:
1. Mounting
2. Connection and
3. Parameter setting
12.1 Mounting instructions
Caution: Danger to life through electric shock!
The following conditions are to be complied with in order to ensure a safe
and reliable operation of the VersiBrake:
1. The device series VersiBrake is to be used under overvoltage conditions of the
category III.
2. Make sure that pollution degree 2 or better, in accordance with IEC664, is
complied with.
3. The device is to be installed into a housing (min. degree of protection: IP54).
4. The device must be operated without being exposed to contamination by
water, oil, carbon deposits, dust, etc.
5. Insert in North America, UL and CSA-listed.
5.1 „Suitable For Use On A Circuit Capable Of Delivering Not More Then 5kA rms
Symmetrical Amperes, 480 Volts Maximum.“
5.2 „Use Copper Conductors 60/75°C or 75°C only.
Warning:
Make sure that a minimum distance to adjoining devices is kept. Above and
underneath the housing a minimum distance of 50mm is to be kept.