VB 230/400-25
17
13.3 Permissible braking frequency
The braking frequency depends on the adjusted braking current.
Please find below some typical values for braking devices of the VersiBrake type:
For intermediate values please refer to the load curve below.
Warning:
When setting up the machine or during commissioning it is possible to carry
out 10 braking operations in succession with the rated device current at a
braking time of 15s. After these operating conditions, however, the device
needs a recovery time of 20 minutes.
Braking current
Braking time
Braking frequency
25A
5s
15s
1 braking per 60s
1 braking per 180s
20A
5s
15s
1 braking per 40s
1 braking per 120s
15A
5s
15s
1 braking per 25s
1 braking per 70s
10A
5s
15s
1 braking per 17s
1 braking per 50s
7,5A
5s
15s
1 braking per 10s
1 braking per 28s
Reduction of the permissible max. braking current
in the case of braking times exceeding 20 secound
0
10
20
30
40
50
60
70
80
90
100
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
Braking time in secounds
Permissible max. braking current in % of the rated device curre
nt