13 685408014B
1 Cooling unit DTS 5 springs shim
2 switch cabinet wall or door 6 nuts
3 thread rod 7 bolts
4 flat gasket 8-12 sealing strip
5) It must fix the M8 nut when strike it on the top of
housing during installing the tooling unit.
6) Clamp the cable as shown in the connection diagram
(see back of unit) to the plug (component pack) and
connect to the unit.
-cable size: 1.0-2.5mm
2
or AWG18-AWG14 (in the
selection of cable size, the relevant regulations must be
observed)
7) Plugging in the power supply on the cooling unit. (see
Section 8.3)
For unit with different mounting method please refer to
technical data sheet supplied in the accessory bag with
the unit.
8.3 Electrical connection
Caution:
• The cooling unit must be connected to the mains
by means of a disconnecting device with a contact gap of
at least 3mm when switch off.
•No temperature sensor must be series-connected to the
cooling unit feed.
•The fuse as indicated on the name plate must be
series-connected as line protection.
• Power connection and repairs, if applicable, may only be
carried out by authorized trained electricians.
Power supply connection:
Both mains voltage and frequency must correspond to the
nominal values indicated on the name plate of the cooling
unit.
Attention:
The cooling unit may be damaged if the
voltage is too high. It‟s nominal voltage is 230V or 400V.
Door contact:
In order to avoid any disruptive influences, it is
recommended that a sheathed cable with twisted pair
leads be used.
Caution: No external voltage may be applied.
If no door contact switch is used, the connecting contacts
are to be bridged.
Fault indication:
For connection of the fault signal line there are 1
connection contact and/or connection lines available (see
circuit diagram on the technical supplementary sheet)
The installation of the fault signal line is not subject to any
special requirement.
Caution:
The contact may be loaded with
max.
230V, 1A
9 Operating condition
•The voltage must be within ± 10
%
of the value indicated.
•The frequency must be within ±3Hz of the value
indicated.
•
Ambient temperature must be below 55
℃
.
•Use the unit such that the cooling capacity suits the
actual demand.
•Use genuine spare parts only.
10 Putting into operation and function
•Please refer to section 7 for the cooling unit which
including the function and options.
10.1 General remarks
The cooling unit is provided with an electronic control
system.The cooling unit‘s internal temperature is