Operating and Maintenance Instructions - Chiller - Series EB 210 - EB 440
© Pfannenberg GmbH
Page 83 / 293
EN
5.6 Connecting the chiller to the power supply
DANGER
Life-threatening danger due to electric shock
Live units and exposed connection cables can generate an electric shock and cause severe accidents.
Work on electrical connections must be carried out exclusively by trained, qualified electricians.
Before assembly, de-energize all supply lines to the separate fuse or a main switch, disconnect the system and
secure to prevent re-connection.
Test to ensure the absence of voltage on the unit and on all power supply cables.
Lightning protection of the unit (outdoor installation) must be carried out by qualified engineers.
NOTICE
Additional information
If units are provided without power and alarm cables (or industrial connectors), cable on terminal blocks into the
electrical box, according to the enclosed
Electric diagram
.
Electrical installation must respect all valid safety standards.
It’s necessary to install protective fuses (indicated on the electrical diagram) or a circuit breaker upstream of the
power cable.
Make sure the system is adequately earthed.
In case of outdoor installation it is strictly recommended to follow the local regulation for the proper protection of
the system (unit + piping) against lightnings.
Check that the voltage and frequency of the power supply correspond to the specifications on the unit’s data
plate and/or enclosed
Electrical diagram
.
Pfannenberg chiller units are designed for TN Earthing Systems. Use the Maximum fault loop chiller Impedance
value for sizing purposes on site (refer to Zpe value specified within
Electrical diagram
attached)
For units with (black) control main switch, emergency switch-disconnector (in accordance with IEC 60947-1,
IEC 60947-2, IEC 60947-3) will be provided by customer in proximity of the unit.
Check the correct sequence of electrical power: L1=R
– L2=S – L3=T; unit provided by phase sequence
monitor will not start with wrong sequence; in this case an alarm on the sequence monitor device will occur.
In this condition change the position of supply conductors (leave all the internal wiring as it is).
CAUTION
Malfunction due to incorrect transformer setting
In case units that can work with different voltages (400 V
50 Hz or 460 V 60 Hz), connect the transformer of the
auxiliary circuit located inside the e-box in the right way.
NOTICE
Transformer factory setting
Unit CE: Factory setting 400/3/50
Unit UL: Factory setting 460/3/60
Summary of Contents for EB 210
Page 97: ...DE Betriebs Wartungsanleitung Chiller Serie EB 210 EB 440 Version 1 0 Juni 2019...
Page 196: ...ES Manual de uso y mantenimiento Refrigerador Serie EB 210 EB 440 Versi n 1 0 Junio 2019...
Page 244: ...RU EB 210 EB 440 1 0 2019...
Page 245: ...Pfannenberg Pfannenberg Pfannenberg...
Page 248: ...EB 210 EB 440 Pfannenberg GmbH Page 248 293 RU 1 1 1 1 2 1 3 c...
Page 249: ...EB 210 EB 440 Pfannenberg GmbH Page 249 293 RU 1 4...
Page 251: ...EB 210 EB 440 Pfannenberg GmbH Page 251 293 RU 2 1...
Page 252: ...EB 210 EB 440 Pfannenberg GmbH Page 252 293 RU 2 2 2 2 1 2 3 2006 42 CE...
Page 253: ...EB 210 EB 440 Pfannenberg GmbH Page 253 293 RU 2014 68 UE I...
Page 254: ...EB 210 EB 440 Pfannenberg GmbH Page 254 293 RU 3 Pfannenberg 3 1 3 2 1 2 3 4 5 6 1 2 2 3 4 5...
Page 255: ...EB 210 EB 440 Pfannenberg GmbH Page 255 293 RU 3 3 3 3 1 3 3 2...
Page 256: ...EB 210 EB 440 Pfannenberg GmbH Page 256 293 RU 3 3 3 3 3 4 3 3 5 3 3 6...
Page 257: ...EB 210 EB 440 Pfannenberg GmbH Page 257 293 RU 3 4...
Page 259: ...EB 210 EB 440 Pfannenberg GmbH Page 259 293 RU...
Page 263: ...EB 210 EB 440 Pfannenberg GmbH Page 263 293 RU 4 4 3...
Page 264: ...EB 210 EB 440 Pfannenberg GmbH Page 264 293 RU 4 5 4 5 1 EB 210 4 5 2 EB 260...
Page 265: ...EB 210 EB 440 Pfannenberg GmbH Page 265 293 RU 4 5 3 EB 310 4 5 4 EB 360...
Page 266: ...EB 210 EB 440 Pfannenberg GmbH Page 266 293 RU 4 5 5 EB 410 4 5 6 EB 440...
Page 268: ...EB 210 EB 440 Pfannenberg GmbH Page 268 293 RU 4 7 4 7 1 EB 210 260...
Page 269: ...EB 210 EB 440 Pfannenberg GmbH Page 269 293 RU 4 7 2 EB 310 440...
Page 272: ...EB 210 EB 440 Pfannenberg GmbH Page 272 293 RU 5 5 1 5 2...
Page 274: ...EB 210 EB 440 Pfannenberg GmbH Page 274 293 RU 33 7 5 mm S355JR 1 0045 5 3...
Page 279: ...EB 210 EB 440 Pfannenberg GmbH Page 279 293 RU 6 30...
Page 280: ...EB 210 EB 440 Pfannenberg GmbH Page 280 293 RU Harting...
Page 282: ...EB 210 EB 440 Pfannenberg GmbH Page 282 293 RU 7 PFANNENBERG PFANNENBERG...
Page 283: ...EB 210 EB 440 Pfannenberg GmbH Page 283 293 RU 6 1 1...
Page 284: ...EB 210 EB 440 Pfannenberg GmbH Page 284 293 RU 6 2 10 Eliwell SMP 6 3 7 7 1 7 2 30 7 3...
Page 285: ...EB 210 EB 440 Pfannenberg GmbH Page 285 293 RU 8 30...
Page 286: ...EB 210 EB 440 Pfannenberg GmbH Page 286 293 RU TD TD Pfannenberg 2 1 Klixon...
Page 287: ...EB 210 EB 440 Pfannenberg GmbH Page 287 293 RU...
Page 289: ...EB 210 EB 440 Pfannenberg GmbH Page 289 293 RU 9 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17...
Page 290: ...EB 210 EB 440 Pfannenberg GmbH Page 290 293 RU 10 10 1 10 2 Pfannenberg...