Characteristics
Technical Data / Configuration
Size 3 Size 3-S
Nominal current
Max. operating voltage
Rated Withstand voltage
Rated lightning impulse
Partial discharge
DC testing
Rated short time current
Rated impulse current
VI
I
n
[A] 1250 1250
U
m
[kV] 42 52
50 Hz/5 min [kV] 95 117
1.2/50 μs [kV] 200 250
2 x U
0
[pC] ≤ 10 ≤ 10
15 min 6 x U
0
[kV] 125 156
0.5 sec [kA] 63 63
1 sec [kA] 50 50
[kA] 150 150
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01