www.pfisterer.com
23
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01
110
(40)
1
"thick" peelable conductive layer
VIII
Installation / Assembly
Only with a thick (> 2 mm) peelable semi-conductive layer
Or with strippable semi-conductive layer
Clean the area towards the "jacket cut" (1).
22
1
1
Do not roughen the surface!
110
(40)
1
strippable conductive layer
Apply adhesive tape 110 mm from the beginning of the insulation.
Ensure the edge is straight and clean. Provide insulation in the direction
of the conductor with protective wrapping.
23
1
24
1
Apply an additional conductive layer of dry graphite that forms a good
covering - approx. 40 mm - on the semi-conductive layer and insulation.
Take care to ensure insulation length of 110 mm is acheived.
Remove the protective wrapping from the insulation.
Shake the bottle well before use. After applying let dry tho-
roughly (minimum 10 min.)!
Remove excess graphite!
OR with some fine wire stranded conductors (RF) / customer specific
use instead of dry graphite, silver for reproduction of a semi-con-
ductive layer:
▪
Using silver for reproduction of a semi-conductive layer, first roughen
the insulation and then the conductive layer from 30 mm with 120 grit
electrical emery (enclosed).
▪
Apply one layer of silver for reproduction of a semi-conductive layer
with the enclosed brush.
Summary of Contents for MV-CONNEX 3
Page 2: ...2 www pfisterer com...