www.pfisterer.com
35
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01
8.7
Sealing kit for offshore / ground applications
An additional sealing kit is required for offshore / ground applica-
tions. Prepare the screen wires for earthing before the large he-
at-shrink tubing is shrunk onto the bell flange.
A
= Fixed Earth
VIII
Installation / Assembly
Fix the screen wires 20 mm after the sealing tape with duct tape.
1
1
Bundle the screen wires together.
2
1
Apply the long slim heat-shrink tubing over the screen wires.
3
1
Apply the cable lug.
4
1
Place two more layer of sealing tape under and over the bundled
screen wires.
5
1
A
30
A
Heat the short shrink tubing at the cable lug and the long slim shrink
tubing.
6
1
Position the Glue Peg on the large heat-shrink tubing between the cab-
le and the heat-shrink covered screen wires.
7
1
Evenly heat the shrink tubing starting from the bell flange until the he-
at-shrink tubing fits evenly all round (below the ribbing) and the inner
adhesive is exposed from both sides.
8
1
Summary of Contents for MV-CONNEX 3