www.pfisterer.com
39
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01
2
The tension cone, insulating part and heat-shrink tubing should
not be reused
!
Dismantling / Removal
IX
Pull the contact ring off the tension cone with the hydraulic compres-
sion tool.
11
1
Slide the retaining ring of the compression head back and open the
half-shells.
12
1
Release the hydraulic compression tool [2].
Remove the hydraulic compression tool.
13
1
Remove the tension cone and thrust piece.
14
1
Cover conductor end with protective wrapping.
15
1
Remove the insulating part and bell flange.