www.pfisterer.com
43
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01
Capacitive voltage tap optional
11
Single Earthing
Earthing principle depends on the network. The design of the
cable, earthing principle, position and the use of the screen
excess voltage limiter must be specified by the customer / pro-
ject management.
Option 1
Cut off screen wires at the height of the sealing tape.
1
1
Fix second layer of sealing tape directly on the first, thus fixing the wires.
2
1
Shrink heat-shrink tubing over bell flange and cable.
3
1
Option 2
Fix the screen wires after the sealing tape with duct tape.
1
1
Bundle the screen wires together, press on the cable lug and shrink over
the long heat-shrink tubing.
2
1
Place one layer of sealing tape above and below the heat-shrink tubing.
3
1
Position a tapping bracket on the large heat-shrink tubing between the
cable and the heat-shrink tubing covered screen wires.
4
1
Shrink heat-shrink tubing over bell flange and cable.
5
1
Connect screen excess voltage limiter.
6
1
1
1
Capacitive voltage tap optional
Single Earthing
XI