www.pfisterer.com
45
Drawings not to scale - for information only Size 3 | 3-S / Standard instructions wire screen / No. 040 371 001 (2014-05-08) i-01
Clean insulating part (recommended cleaning agent: benzene, acetone)
and protective cap (not voltage-proof) or blind cap (permanent) raise.
3
1
Clean the inside of the socket (recommended cleaning agents: benze-
ne, acetone) and grease thinly and evenly with PFISTERER MV-special
grease. Wear clean protective gloves (e.g. latex or plastic).
4
1
Insert cover (not voltage-proof) or dummy plug (voltage-proof).
5
1
Unplugging/ Plugging In
XII
When using the blind cap, grease is required!
When using the dummy plug, grease is required!