PFT Air Compressor LK
402 IV
Overview – Operation – Spare
Parts Lists
Page 24
28.01.2019
5 Start-up
5.1 Set-up
Fig. 4: Set up
To avoid damage to the compressor, it must never be operated with
a transverse or longitudinal inclination of more than 15°.
To ensure proper ventilation, the compressors must be positioned so that
the rear ventilation grille is at least 50 cm from any obstacle to the airflow
and that cleaning and maintenance are easy.
5.2 installation
Fig. 5: Installation
Every compressor is not delivered until it has successfully passed a series
of functional tests by the manufacturer. For optimum operation, please
observe the measures and recommendations listed below.
- Fit the wheels and anti-vibration protection (Fig.3), remove the plug from
the compressor head and fit the intake filter if it is not already fitted (Fig.5).
Fig. 6: Test rod
Remove the cap from the housing and insert the oil level dipstick (Fig.6).
- Carefully ensure that the oil level is between the minimum and maximum
value of the test rod (Fig. 6).
- After the first 5 hours of operation, change the oil completely with one of
the oil types listed in the table (see point 6.3).
• Check the compressor voltage and make sure that the supply network is
protected by a magnetic heat insulator and has an earth connection.
The compressor is equipped with a mains plug type CEE 7. Have the
plug replaced by qualified personnel if necessary or to adapt it to local
regulations.
Summary of Contents for LK 402 IV
Page 35: ...28 01 2019 Page 35...