PFT SILOMAT E
10
Setting Values
10.2005
____________________________________________________________________________________________________________
_______________________________________________________________________________________
Knauf PFT GmbH & Co.KG
Telephone 09323 / 31-760
Postfach 60
Telefax
09323 / 31-770
D-97343 Iphofen
Internet
www.pft.de
_______________________________________________________________________________________
Relay
Function Designation
Setting
value
Requirement K2
3
sec.
Fill time
K5
6 sec.
Transport time
K8
18 sec.
Air pressure safety switches
0.8 bar switch on machine
0.5 bar switch off machine
Motor safety switch compressor motor
5.5 kW motor 400 V, 11.5 A
7.5 kW motor 400 V; 16 A
Oil level compressor
The oil level of the compressor must be between the two oil control glasses.
Hand 0 automatic switch
Hand
in this position, the compressor runs continuously and can be used for blowing
out the conveying line and for venting the silo.
0
System isn’t running.
Automatic
in this position, the system runs automatically.
Vibrator socket
The vibrator runs automatically in the course of filling.
K8
K2
K5