ON-LINE 3P/3P
PH 9283 - PH 9284 .
This screen is used for transform voltage and Power display.
●
You can select Wire system between “3Ph_4Wire” and “3Ph_3Wire”.
●
You can select input voltage ratio between the following options:
“230/230”
“230/277”
“120/230”
“120/220”
●
You can select output voltage ratio between the following options:
“230/230”
“277/230”
“230/120”
“220/110”
●
You can select output power ratio. The range of ratio goes form 50% to 200%.
●
Fig.20 Electrical 3
Screens 3.1.2-2:
this screen is used for battery setting.
You can select the battery high and low warning voltage range. The range of high voltage goes from
13.0V to 15.0V.
The range of shutdown voltage goes from 10.5V to 12V. The range of low voltage depends on shutdown
voltage.
Fig.21 Battery setting
85 / 100