ON-LINE RACK
PH 9360 - PH 9301 .
Display
Setting
01:
Output voltage
Parameter 2: Output voltage
You may choose the following output voltage in parameter 2:
208
: Presents output voltage is
208
Vac
220
: Presents output voltage is
220
Vac
230
: Presents output voltage is
230
Vac
240
: Presents output voltage is
240
Va
c
02: l
Output frequency
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three options
in parameter 2:
50.0Hz
: The output frequency is setting for 50.0Hz.
60.0Hz
: The output frequency is setting for 60.0Hz.
At:
If selected, output frequency will be decided according to the latest
normal utility frequency. If it is from 46Hz to 54Hz, the output frequency
will be 50.0Hz. If it is from 56Hz to 64Hz, the output frequency will be
60.0Hz. At is default setting.
Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You may
choose following two options in parameter 2:
CF:
Setting UPS to CVCF mode. If selected, the output frequency will be
fixed at 50Hz or 60Hz according to setting in parameter 2.
The input frequency could be from 46Hz to 64Hz.
NC:
Setting UPS to normal mode (not CVCF mode). If selected, the
output frequency will synchronize with the input frequency within 46~54
Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in parameter
2. If 50 Hz selected in parameter 2, UPS will transfer to battery mode
when input frequency is not within 46~54 Hz. If 60Hz selected in
parameter 2, UPS will transfer to battery mode when input frequency is
not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 2 will show the current frequency.
Note:
: If the UPS is set to CVCF mode, the bypass function will be disabled automatically.
But when a single UPS without parallel function is powered on with mains and before the UPS finished the startup, there will be a few
seconds of voltage pulse (same as the input voltage) on the bypass output. If you need to remove the pulse on this mode to protect your
load better, you could contact the dealer for help.
For the UPS with parallel function, this pulse situation won’t happen.
87 / 100