If the charger is functioning properly, check the voltage of the battery as some chargers will not
recognize an over discharged battery.
•
To take a battery out of quarantine, disconnect the battery from the charger and reconnect the
battery.
4.2.4 Unknown
The Unknown column shows the number of chargers with an unknown status according to the system.
•
If any charger ID’s are listed in the column marked “Unknown”, check to see if the Sentinel™ shows
a steady green light. If it does, wait a few min
utes and check the “Status” screen again. There
could have been a miscommunication between the control box and the Sentinel™ in which case the
status will update the next time the control box polls the Sentinels™.
•
If the Sentinel™ does not have its green LED illuminated,
o
Check the data cables to make sure that they are secure and have not been broken or
pinched.
o
Be sure that the data cable is plugged into the control box.
o
Be sure that the data cable is connected to the first
Sentinel™ and that the cable is
connected between each Sentinel™.
o
Make sure that the control box has power.
•
If the green light is flashing, be sure that the
Sentinel™ has been assigned to a Pool through the
charger configuration. (See DOC0023
– iBOS
®
Pro 6 Series Installation Manual for more details.)
4.3
Sentinel™ Lights
Following is a description of the LED indicators:
4.3.1 Green LED
– Communication status
•
Off
– No power to the Sentinel™.
•
Solid
– Sentinel™ is communicating properly with Controller.
•
Flashing
– Sentinel™ is not communicating properly with the Controller.
4.3.2 Amber LED
– Charging status
•
Off
– No battery connected.
•
Solid
– Battery is connected. (If the amber light is on, but no battery is connected, check the
charger for a voltage leak to the DC cables.)
4.3.3 Blue LED
– Termination status
•
Off
– Battery is not at the top of the queue.
•
Bright with Momentary Flashing
– This is the correct battery to pick next.
4.3.4 Red LED
– Bad communication cable
•
Solid
– Power wires reversed in the data cable.
•
If the red light is on, replace the data cable.