background image

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

      features  

 

 

 

 

 
 

 

 

To  reduce  the  risk of  fire or  electric shock,  do  not  expose 
this device to rain or moisture. Do not energise unless the 
front  cover  is  in  place.    This  device  must  be  earthed. 
Installation,  programming  and  maintenance  must  be 
carried out by qualified personnel. 

 

Single Phase Supply

 - 1 phase at 0.15A 

 

 

5 x Feed thru Outputs

 Rated at 16A 

 

 

Power outputs are Latching Relays

 

 

 

Manual Overrides for each channel

 

 

 

Powerful  Internal  PLC  - 

Custom  scripts  can  be  written  to 

provide process control based on conditional logic 

 

 

Dry Contact Interface - 

An Auxiliary dry contact interface is 

provided. The factory settings will cause this input to transmit 
network identification information 

 

 

Many Control Options - 

Control of this device can be via a 

combination  of  methods,  eg.  serial  control  port,  relay 
contacts,  push  button  wall  stations,  infrared  receivers  and 
time clocks 

 

 

Simple  Installation  - 

DIN  Rail  mount  facilitates  installation. 

All connection terminals are accessible without disassembly 

Warning 

– 

This  device  is  a  class  A  product.    In  a  domestic  environment  this 

product may cause radio interference, in which case the user may be required to 
take adequate measures.  

Read Instructions

 

– We recommend that you read this Instruction Manual prior 

to commencement of installation.   

Manual  Override  Switches

  -  These  switches  do  not  provide  permanent 

isolation. Isolate at the supply before performing work on load circuits. 

Special  Programming

 

–  This  device  will  only  operate  in  basic  modes  unless 

programmed  via  a  computer.    If  programming  is  required,  contact  your  local 
agent  for  details.    Once  the  data  cable  is  connected  to  the  devices,  the  factory 
default  settings  will  allow  any  control  panel  to  operate  all  channels  in  all 
controllers. 

Power

 

Sources

 

– This device should only be operated from the type of supply 

specified on the front cover.  This device 

must

 be earthed. 

Feed  Thru  Output  Circuits

 

–  The  load  on  a  circuit  should  not  exceed  the 

specified capacity of 16A.  Loads should be calculated to ensure that the overall 
maximum capacity of 80A is not exceeded.  This device should be fed via a HRC 
fuse  or  MCB.  Output  circuits  are  suitable  for  Single  Phase  or Three  Phase  Star 
(with Neutral) only, Delta wiring is not supported. 

Mounting  Location

 

–  Install  in  a  dry,  well-ventilated  location.    Controllers  may 

emit some mechanical noise.  Take this into account when deciding the mounting 
location. 

Data Cable

 

– Use screened, stranded RS485 data cable with three twisted pairs. 

Segregate from mains cables by 300mm minimum.  Connect devices in a ‘daisy 
chain’. A data cable that is connected to an energised device is live.  Do not cut 
or terminate live data cables. 

DDBC516FR 

5 x 16A relay & Open Protocol Controller 
Installation Manual 

……… 

electrical diagram 

 