1.  Mount the device on a DIN rail inside an approved enclosure. 
2.  Calculate loads to ensure any channels are not overloaded, then connect loads to the output channels. The maximum 

loading of this device is as follows:  

Maximum Channel Load:

 

16A 230V AC

 

Total Box Load

80A 

Connect supply and load cables to each channel. Note that this device must have an individual supply circuit for each 
channel. The supply circuits can be on any phase. Note that loads must have a Neutral (1 Phase or 3 Phase Star), Delta 
wiring is not supported. 

3.  5 x Control Outputs, each selectable to;  

- DALI broadcast: max 10 DALI loads per channel. 
- DALI addressed: max 10 DALI loads per channel. 
- 1-10V: max 10mA Sink or Source per channel. 
- DSI: max 10 DSI loads per channel. 

4.  Connect a single phase 0.15A feed to the control circuit supply terminals.  This device must be earthed. 
5.  Connect data cables to the device as per diagrams below.  
6.  If the Auxiliary input is to be used, connect a dry contact device in between the AUX and GND terminals. Keep cable runs 

between the device and the dry contacts under two metres. The function of the Auxiliary input will need to be programmed 
at the time of commissioning. 

Control Supply: 

230V ±14% 50/60Hz single phase at 0.15A 

Load Outputs: 

        

5 x Feed Thru Outputs at 16A per channel, max total box load is 80A 

 

               Wiring topology: 1 Phase & Neutral and 3 Phase & Neutral Star. Delta not supported 

 

        5 x Open protocol, each selectable to DALI address, DALI Broadcast, 1-10V or DSI 

 

Switching Device: 

Relay 

– 50A 230V AC resistive (5000W Lighting Load rated) 

Supply

 

Terminals:

 

1 x Phase, 1 x Neutral 1 x Earth, up to 1 x 4mm

2

 cable per terminal 

Load Terminals: 

IN, OUT for each channel, up to 1 x 4mm

2

 cable per terminal 

IO: 

1 x RS485 DyNet serial port 

 

1 x AUX programmable dry contact input 

DyNet DC Supply: 

200mA (capacity for approx 5 Panels) 

Presets: 

170

 

 

170 

Programmable Logic: 

8 Tasks, most UPAN mnemonics supported 

Compliance: 

CE, C-Tick 

Ambient Temperature: 

50

C max. 

Construction: 

Polycarbonate plastic DIN rail mount 

Dimensions: 

Height 93mm x Width 211mm x Depth 75mm 

Weight: 

0.8Kg 

 

DDBC516FR-DALI Rev B Specifications subject to change without notice

 