Input Voltage: 

12 VDC max, 375 mA from the DyNet network (port 1)

RS485 Serial Port 1: 

1 x RS485 unterminated, consisting of 1 x 6 way terminal block

RS485 Serial Port 2: 

1 x RS485 unterminated, consisting of 1 x RJ12 socket & 1 x 5 way terminal block

Serial Port Isolation: 

Opto Isolated to 3.75 KV

RS485 Data Formats: 

DyNet, DyNet II, DMX512 Receive 64 channels

 

Supported Baud rates: 1200 - 460800

Output Terminals: 

12 x DALI, 0-10V, DSI driver circuits: DA+, DA-

 

conductor size 0.2 - 5mm

2

 (24 - 10 AWG)

User Controls: 

Service switch, Diagnostic LED

Internal Controls: 

Programmable Logic Controller, 64 tasks

Operating Conditions: 

Temperature: 0 to 50° C ambient

 

Humidity: 0 to 90% non-condensing

Storage & Transport: 

Temperature: -25 to 60° C ambient

 

Humidity: 0 to 90% non-condensing

Construction: 

Polycarbonate DIN rail enclosure

Dimensions: 

95 mm x 105 mm x 75 mm (3.8” x 4.1” x 2.9”)

Packed Weight: 

0.25 kg

Certification: 

CE, RCM

Recommended Cable Type

Dynalite DYNET-STP-CABLE or equivalent shielded 

three twisted-pair.

See datasheet for more information.

Recommended Cable Color Coding

Green/White Pair

 

Paralleled for GND

Orange/White Pair

 

Paralleled for +12VDC

Blue/White Pair

 

Blue for DATA+

 

White for DATA-

Brown/White Pair

 

Spare, use for SHIELD on unshielded cables

SH

LD

GN

D

D+

D-

+1

2V

Au

x

Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white

+VE

+VE

D – 

+

GND GND

RS485 DyNet network

Product Specifications

Example of trunk and spur topology

Sensor 

DUS360CR

DyNet Trunk

DyNet Spur

To up to 59 more devices

DDNG485 

Network Gateway

DyNet Trunk

DyNet Spur

To up to 59 more devices

To other

floors

To other

floors

DyNet Trunk

DDNG485 

Network Gateway

Sensor 

DUS360CR

Sensor 

DUS360CR

Sensor 

DUS360CR

DDRC820FR-GL

DDNG485

DDNG485

DDRC820FR-GL

DDRC820FR-GL

DDRC820FR-GL

Reviews: