background image

4

DMC2 Installation Instructions Rev 03

Mounting

For surface mounting, four mounting points have been 

provided. Refer to the location of the mounting points in the 

dimension drawings on page 7 of this document.

For recess mounting, four holes suitable for M6 (1/4”) 

fasteners have been provided on side walls as shown below. 

Minimum spacing between studs is 380mm (15”), minimum 

mounting depth 103mm (4.1”)

Allow for Cable Entry

Supply and load cables can enter the enclosure through 

knockouts at the top, side or back. An alternative method 

is to stand the enclosure off from the mounting surface by 

mounting it on a cable tray or a Unistrut-style product.

The control cables enter at the bottom of the enclosure. 

Control cables should never be run in the mains voltage 

sections of the enclosure.

Energizing the Device

If it is necessary to energize load circuits for test purposes 

before any control cables are connected, it is acceptable 

to replace the top cover and energize the device, as the 

default factory programming is to have all channels set 

to 100% output. Use the manual override keypad on the 

communication module to control individual channels.

This device should be de-energized before terminating the 

control and data cables.

Select a suitable location

This device is designed for indoor use only. If 

installing in an outdoor location, the DMC2 must 

be housed in a suitable well-ventilated enclosure. 

Choose a dry location that will be accessible after the 

installation is complete. To ensure sufficient cooling, 

the DMC2 must be mounted vertically, as shown 

above. The DMC2 requires a minimum air gap of 

200mm (8”) around the front, sides, top and bottom of 

the front cover. This air gap is also required to ensure 

serviceability of the DMC2 without complete removal 

from the mounting surface.

The device may emit some audible noise during 

operation. Take this into account when deciding the 

mounting location.

Ensure no dust or other debris enters the device during 

installation. Do not leave the front cover off for any length 

of time. Excessive dust and dirt can impede the cooling of 

internal components.

Summary of Contents for Dynalite DMC2

Page 1: ...fications 8 Internal View 3 Mounting 4 Module mounting 5 DMC2 Installation Instructions Rev B Specifications subject to change without notice Dynalite manufactured by WMGD Pty Ltd ABN 33 097 246 921 Unit 6 691 Gardeners Road Mascot NSW 2020 Australia Tel 61 2 8338 9899 Fax 61 2 8338 9333 E Mail support controls philips com Web http philips com dynalite ...

Page 2: ...ser interface on the same network will turn all output lighting channels on from button 1 and off from button 4 allowing testing of network cables and terminations Advanced functions and custom presets can then be configured via the EnvisionProject commissioning software If commissioning services are required contact your local distributor for details High Voltage Insulation Test Do not Megger tes...

Page 3: ...power connection Communication bus connection Communication bus connection Surface mounting sleeve Wall mounting point Knockouts for unit supply Wall mounting point Communication bus cover Knockouts for lighting group channels High voltage barrier Data cable entry points Surface mounting sleeve For spare parts please call your nearest Philips Dynalite Customer Service Centre Communication bus conn...

Page 4: ...over and energize the device as the default factory programming is to have all channels set to 100 output Use the manual override keypad on the communication module to control individual channels This device should be de energized before terminating the control and data cables Select a suitable location This device is designed for indoor use only If installing in an outdoor location the DMC2 must ...

Page 5: ...phase for three phase supply or up to 63A for single phase to allow the device to be loaded to its maximum capacity The earth bar is located in the DMC unit near the top of the case To install the Communication Supply and Control modules 1 Connect the module ribbon cable to its respective plug 2 On the left hand side of the module there are two locating tabs which will line up with the DMC communi...

Page 6: ...plied wiring loom to the DMC2 as shown Use only the loom supplied with the unit and do not break or modify the loom in any way Make sure the labels on the loom correspond to the wiring on each module For modules requiring termination remove the black insulating caps from the loom before terminating to the load and supply modules For any module location that is not populated or does not require ter...

Page 7: ...7 DMC2 Installation Instructions Rev 03 Dimensions 380mm 15 0in 540mm 21 3in 103mm 4 1in 285mm 11 2in 440mm 17 3in ...

Page 8: ... Radio Frequency Notice This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the ins...

Reviews: