Specification
Control Modules:
2 x Control module locations
Cable Entry: Supply/Control
Top:
4 x 28.2mm (1.1”)
2 x 22.2mm (0.87”)
Side:
7 x 28.2 (1.1”)
7 x 22.2mm (0.87”)
Back:
4 x 28.2mm (1.1”)
3 x 22.2mm (0.87”)
Data
Side:
1 x 28.2mm (1.1”)
Bottom:
1 x 28.2mm (1.1”)
Note:
28.2mm (1.1”) opening is suitable for 3/4” conduit
22.2mm (0.87”) opening is suitable for 1/2” conduit
Compliance: DMC2-UL:
UL, CSA, CE, RCM, FCC, ICES-003
Overvoltage category III, Pollution Degree II
DMC2-CE:
CE, RCM, Overvoltage category III, Pollution Degree II
NOTE:
• The temperature limits and current-carrying capacities of the communication
wires specified in HD 384.5.523 shall not be exceeded.
• Installation of home and building automation control shall comply with HD 60364-
4-41.
• Network Topology for installation is Daisy Chain.
Input: Voltage rating:
120/230/277 VAC +10% / -15%
50/60 Hz 3-Phase, 4-Wire (Y), or Single Phase
Current rating:
32 A per phase for 3-phase supply, or single phase 63 A max
Operating Environment:
0°C to 40°C (32°F to 104°F) ambient temperature
0% to 90% RH non-condensing
Shipping and Storage:
-25°C to 60°C (-13°F to 140°F) ambient temperature
0% to 90% RH non-condensing
Construction:
Galvanized Steel case with powder coated front covers
Dimensions: H:
540mm (21.3”)
W:
380mm (15”)
D:
106mm (4.2”)
Weight:
7.71 kg (17 lbs) (excluding all modules)
Federal Communications Commission (FCC) Compliance Notice: Radio Frequency Notice
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
•
Reorient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
•
Consult the dealer or an experienced radio/TV technician for help.
CAUTION: Any modifications not approved by the manufacturer of this device could void the user’s authority to operate this device.
Compliance to Industry Canada ICES-003: CAN ICES-3(B)/NMB-3(B)
DMC2 Installation Instructions Rev 03 Specifications subject to change without notice