Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
Philips Lighting Canada Ltd.
281 Hillmount Road,
Markham, ON, Canada L6C 2S3
Phone: 800-668-9008
9140053342 February 2016
AC SERVICE
HOOKUP INSTRUCTIONS
Standard Units:
Connect AC service to unit terminal block.
The unit is pre-wired to accept 120 or 277
VAC. Insert AC service leads and ground
wire to appropriately labeled terminal(s).
Tighten.
REMOTE LAMP CONNECTION
1.
A terminal block for the remote lamp loads
is provided for easy installation. Two
terminals are available for DC+ and DC-
each. Units ship from the factory with load
connection jumpers installed on both DC+
and DC-. This parallels the load among the
unit RL1+ and RL2+ output load fuses.
Using the jumpers ensures that the total load
of the unit is evenly distributed.
2.
REMOTE LOADS WITH LOAD
CONNECTION JUMPERS INSTALLED
(SMALLER REMOTE LOAD REQUIREMENTS)
1.
When using the jumpers, simply subtract the
internal lamp total wattage from the unit
total wattage and the remainder is the
available total remote load capacity.
Balancing of RL1 and RL2 is not required as
the jumpers perform the remote load
balancing.
2.
When figuring total load, include the
wattage of the internal lamps if applicable
and do not exceed unit total wattage
capability.
3.
EXAMPLE:
A 200 watt unit with three (3) 12 watt
lamps connected has 164 watts of remote
load capability.
REMOTE LOADS REQUIRING
SEPARATE FUSING
(LARGER REMOTE LOAD REQUIREMENTS)
1.
When it is necessary to independently fuse
each set of remote lamp loads, removal of
the load connection jumpers is required.
2.
Removal of the load connection jumpers is
accomplished unscrewing and removing the
jumper itself.
3.
The terminals are marked RL1 DC+, RL2
DC+, RL1 DC- and RL2 DC-. The terminal
blocks are capable of accepting up to #6
wire.
Balancing of the remote lamp loads among
RL1 and RL2 is now a consideration and
must
be
planned
ahead
of
time.