background image

 

 

 

  

 

Philips Lighting North America Corporation 
200 Franklin Square Drive 
Somerset, NJ  08873, USA 
Phone:  855-486-2216 

www.philips.com/luminaires

  

Philips Lighting Canada Ltd. 
281 Hillmount Road, 
Markham, ON, Canada  L6C 2S3 
Phone:  800-668-9008 

www.philips.com/luminaires

 

9140053342  February 2016 

 

AC SERVICE 

HOOKUP INSTRUCTIONS 

 

 

 
Standard Units: 

 

Connect  AC  service  to  unit  terminal  block.  
The  unit  is  pre-wired  to  accept  120  or  277 
VAC.    Insert  AC  service  leads  and  ground 
wire  to  appropriately  labeled  terminal(s).  
Tighten. 

 

 

REMOTE LAMP CONNECTION 

 

 

1.

 

A  terminal  block  for  the  remote  lamp  loads 
is  provided  for  easy  installation.    Two 
terminals  are  available  for  DC+  and  DC- 
each.  Units ship from the factory with load 
connection  jumpers  installed  on  both  DC+ 
and DC-.  This parallels the load among the 
unit  RL1+  and  RL2+  output  load  fuses.  
Using the jumpers ensures that the total load 
of the unit is evenly distributed.   

2.

 

 

REMOTE LOADS WITH LOAD 

CONNECTION JUMPERS INSTALLED 

(SMALLER REMOTE LOAD REQUIREMENTS) 

 

1.

 

When using the jumpers, simply subtract the 
internal  lamp  total  wattage  from  the  unit 
total  wattage  and  the  remainder  is  the 
available total remote load capacity.   
Balancing of RL1 and RL2 is not required as 
the  jumpers  perform  the  remote  load 
balancing. 

 
2.

 

When  figuring  total  load,  include  the 
wattage  of  the  internal  lamps  if  applicable 
and  do  not  exceed  unit  total  wattage 
capability.  

3.

 

EXAMPLE: 
A  200  watt  unit  with  three  (3)  12  watt  
lamps  connected  has  164  watts  of  remote 
load capability. 

 

REMOTE LOADS REQUIRING  

SEPARATE FUSING 

(LARGER REMOTE LOAD REQUIREMENTS) 

 

1.

 

When  it  is  necessary  to  independently  fuse 
each  set  of  remote  lamp  loads,  removal  of 
the load connection jumpers is required.   

2.

 

Removal  of  the  load  connection  jumpers  is 
accomplished  unscrewing  and  removing  the 
jumper itself.  

3.

 

The  terminals  are  marked  RL1  DC+,  RL2 
DC+, RL1 DC- and RL2 DC-.  The terminal 
blocks  are  capable  of  accepting  up  to  #6 
wire.   
Balancing  of  the  remote  lamp  loads  among 
RL1  and  RL2  is  now  a  consideration  and 
must 

be 

planned 

ahead 

of 

time.  

Summary of Contents for TMFIC Series

Page 1: ...recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters CAUTION Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against ...

Page 2: ...ole of housing in preparation for unit wiring For surface conduit wiring there are a total of six knockouts which can be used for service entrance and exit Figure 1 OPTIONAL MOUNTING SHELF FOR COLUMN POLE OR I BEAM 1 If the unit is to be mounted to poles columns or I Beams use the optional mounting shelf kit and strapping kit ordered separately 2 If mounting shelf is to be used for wall mounting t...

Page 3: ...TE LOADS WITH LOAD CONNECTION JUMPERS INSTALLED SMALLER REMOTE LOAD REQUIREMENTS 1 When using the jumpers simply subtract the internal lamp total wattage from the unit total wattage and the remainder is the available total remote load capacity Balancing of RL1 and RL2 is not required as the jumpers perform the remote load balancing 2 When figuring total load include the wattage of the internal lam...

Page 4: ... internal lamp 1 and internal lamp 3 are on the RL1 fused circuit Internal lamp 2 is connected to the RL2 fused circuit For RL1 circuit subtract twice the internal lamp rating from half the unit wattage and the remainder is the available remote load capacity For RL2 circuit subtract one internal lamp wattage from half the unit wattage and the remainder is the RL2 remote capacity Example A 300 watt...

Page 5: ...ally initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec trans...

Page 6: ...ion 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053342 February 2016 ...

Page 7: ...NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053342 February 2016 BATTERY HOOKUP DIAGRAMS 12V 200W 12V 250W 12V 300W 24V 300W 12V 450W 24V 450W ...

Reviews: