background image

Solar Charge Controller CML05-2, CML08-2, CML10-2, CML15-2, CML20 

User Manual English, Page 1 

Dear Client, 
Thank you very much for buying a Phocos product. With your new CML controller 

you own a state-of-the art device which was developed according to the latest 
available technical standards. It comes with a number of outstanding features, like: 

Clear, readable display of the state of charge 
Acoustic signal when the state of charge changes 
Low voltage disconnect regulated by state of charge or voltage 
16 mm² connector clamps 
Complete electronic protection 

This manual gives important recommendations for installing, using and programming as 
well as remedies in case of problems with the controller. Read it carefully in your own 
interest and mind the safety and usage recommendations at the end of this manual. 

Description of Functions 

The charge controller protects the battery from being overcharged by the solar 
array and from being deep discharged by the loads. The charging characteristics 

include several stages which include automatic adaptation to the ambient tempera-
ture. 
The charge controller adjusts itself automatically to 12V or 24V system voltage. 
The charge controller has a number of safety and display functions.  

Mounting and Connecting  

The controller is intended for indoor use only. Protect it from direct sunlight and place 
it in a dry environment. Never install it in humid rooms (like bathrooms).  
The controller measures the ambient temperature to determine the charging voltage. 

Controller and battery must be installed in the same room.   
The controller warms up during operation, and should therefore be installed on a non 
flammable surface only. 
 
REMARK: Connect the controller by following the steps described below to avoid 
installation faults. 

1

Mount the controller to the wall with screws that fit to the wall 
material. Use screws with 4 mm shaft and max. 8 mm head 

diameter, no counter sunk. Mind that the screws have to carry 
also the force applied by the wiring. 
Make sure that the ventilator slits on the sides are unob-

structed. 
 

A DIN Rail mounting plate is available as an accessory (CX-DR2). This allows mount-

ing the controller on a standard 35mm DIN rail. Remove the screws at the backside of 
the controller and screw the mounting plate with the (long) fastening screw onto the 
backside of the controller. 

2

Connect the wires leading to the battery with correct polarity. 

To avoid any voltage on the wires, first connect the controller, 
then the battery. Mind the recommended wire length (min 30 

cm to max approx. 100 cm) and the wire size:  
CML05: min 2.5 mm² 
CLM08: min 4 mm² 

CML10: min 6 mm² 
CML15, CML20: min 10 mm² 
Wrong polarity will cause a permanent warning sound. 

WARNING: If the battery is connected with reverse polarity, the load terminals 

will also have the wrong polarity. Never connect loads during this condition! 

REMARK: Mind the recommendations of your battery manufacturer. We strongly 
recommend connecting a fuse directly to the battery to protect any short circuit at the 
battery wiring. The fuse must take the charge controller nominal current: 
CML05: 20A, CML08: 20A, CML10: 30A, CML15: 30A, CML20: 40A 

3

Connect the wires leading to the solar array with correct 
polarity. To avoid any voltage on the wires, first connect the 
controller, then the solar array. Mind the recommended wire 

size:  
CML05: min 2.5 mm² 

CLM08: min 4 mm² 
CML10: min 6 mm² 

CML15, CML20: min 10 mm² 
 

REMARK: Place positive and negative wire close to each other to minimize electro-
magnetic effects. 
REMARK: Solar panels provide voltage as soon as exposed to sun light. Mind the solar 

panel manufacturer’s recommendations in any case. 

4

Connect the wires leading to the loads with correct polarity. 
To avoid any voltage on the wires, first connect the wire to the 
load, then to the controller. Mind the recommended wire size:
CML05: min 2.5 mm² 

CLM08: min 4 mm² 
CML10: min 6 mm² 

CML15, CML20: min 10 mm² 
 

Grounding the Solar System 

 

Be aware that the positive terminals of the 
CML controller are connected internally and 

therefore have the same electrical potential. If 
any grounding is required, always do this on 

the positive wires. 
 

REMARK: If the device is used in a vehicle which has the battery negative on the 
chassis, loads connected to the controller must not have an electric connection to the 

car body, otherwise the Low Voltage Disconnect and electronic fuse functions of the 
controller are short circuited. 

Starting up the Controller 

Self Test 

As soon as the controller is supplied with power either from the battery or the solar 

array, it starts a self test routine. Then the display changes to normal operation.  

System Voltage

 

The controller adjusts itself automatically to 12 V or 24 V system voltage.  
As soon as the voltage at the time of start-up exceeds 20.0 V, the controller implies a 
24 V system. 
If the battery voltage is not within the normal operation range (ca. 12 to 15.5 V or ca. 

24 to 31 V) at start-up, a status display according to the section ERROR DESCRIP-
TION occurs. 

Battery Type 

The controller is preset to operate with lead acid batteries with liquid electrolyte. If 

you intend to use a lead-acid battery with solid electrolyte ('gel' type or 'fleece' type) 
you can adjust the charging characteristics (see "Settings"). The equalization charge is 

deactivated then. 
In case of any doubts consult your dealer. 

Recommendations for Use 

The controller warms up during normal operation.  
The controller does not need any maintenance or service. Remove dust with a dry 

tissue. 
It is important that the battery gets fully charged frequently (at least monthly). Other-
wise the battery will be permanently damaged.  
A battery can only be fully charged if not too much energy is drawn during charging. 

Keep that in mind, especially if you install additional loads. 

Display Functions 

The controller is equipped with 5 LEDs and an acoustic warning signal. 

Charge display

 

State of charge display

 

Load status display

 

In normal operation, the controller shows the state of charge of the battery and the 
charge from the solar panels. Any change of the state of charge (SOC) to a lower 

status is additionally signaled acoustically. 

Charge display

 

Solar array supplies electricity  Solar array does not supply electricity 

State of charge display 

>75% 25-75% <25% 

flashes: 

<10% 

The percentage corresponds to the available energy until Low Voltage Disconnect in 
relation to a fully charged battery. 

Acoustic signals

 

A change in the state of charge (SOC) to a lower status is indicated by an acoustic 
signal. 

1x

3x

5x

25x

The loads are disconnected approx. 1 minute after a series of 25 signals. 

Load status display

 

In case of deep discharge or overload/short-circuit of load, the load output is switched 
off. This is indicated by: 

Normal operation 

Low voltage disconnect  Overload or Short-circuit of load 

Summary of Contents for CML05-2

Page 1: ...rschnitte CML05 mind 2 5 mm CLM08 mind 4 mm CML10 mind 6 mm CML15 CML20 mind 10 mm HINWEIS Die Plus und Minus Leitung zum Solargenerator m ssen dicht nebeneinan der liegen um elektromagnetische Effekt...

Page 2: ...st tiefentladen Last schaltet automatisch zu wenn die Batterie nachgeladen wurde berstrom Kurzschluss Verbraucher Alle Verbraucher abschalten berstrom Kurzschluss beseitigen Regler schaltet nach ca 1...

Page 3: ...r array Mind the recommended wire size CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm REMARK Place positive and negative wire close to each other to minimize electro magnetic eff...

Page 4: ...r Display Reason Remedy Battery is low Load will reconnect as soon as battery is recharged Overcurrent Short circuit of loads Switch off all loads Remove short circuit Controller will switch on load a...

Page 5: ...ndado CML05 m n 2 5 mm CLM08 m n 4 mm CML10 m n 6 mm CML15 CML20 m n 10 mm OBSERVACI N para minimizar los efectos electromagn ticos coloque el cable positivo al lado del cable negativo OBSERVACI N Los...

Page 6: ...te Cortocircuito de consumos Desconectar todos los consumos Suprimir cortocircuito El controlador activar autom ticamente el consumo despu s de 1 minuto como m ximo El voltaje de la bater a es demasia...

Page 7: ...lle des c bles CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm REMARQUE placez le c ble positif et le c ble n gatif pr s l un de l autre afin de minimiser les effets lectromagn ti...

Page 8: ...cuit de charges Eteindre toutes les charges D brancher le court circuit Le contr leur allumera le r gulateur de charge automatiquement apr s 1 minute au maxi mum Tension de la batterie trop lev e 15 5...

Page 9: ...5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm OPMERKING plaats de positieve en negatieve kabel dicht naast elkaar om de kans op elektromagnetische effecten te verkleinen OPMERKING zonnepane...

Page 10: ...neer de accu weer voldoende is opgeladen Overstroom kortsluiting aangesloten apparatuur Alle aangesloten apparatuur uitschakelen Kortsluiting opheffen Regelaar schakelt last automatisch in na max 1 mi...

Page 11: ...Observe o tamanho do fio recomendado CML05 m n 2 5 mm CML08 m n 4 mm CML10 m n 6 mm CML15 CML20 m n 10 mm OBS coloque os fios positivo e negativo pr ximos um ao outro para minimizar efeitos electromag...

Page 12: ...o Erro Mostrador Raz o Solu o Bateria est com carga baixa Carga ser reconectada assim que a bateria for recarregada Sobreintensidade Curto circuito dos dispositivos Desligue todos os dispositivos Remo...

Page 13: ...solare Attenetevi alla grandezza del cavo raccomandata CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm NOTA mettete il cavo positivo e quello negativo vicini l uno all altro per...

Page 14: ...tutti i carichi Rimuovere cortocircuito Il regolatore accender il carico automaticamente al massimo dopo 1 minuto Tensione batteria troppo alta 15 5 31 0 V Controllate se altre fonti sovraccaricano l...

Reviews: