User Manual English, Page 2 

Low Voltage Disconnect Function (LVD) 

The controller has 2 different modes to protect the battery from being deeply 

discharged:  
1.  State of charge controlled: Disconnect at 11.4 V (at nominal load current) up to 

11.9 V (at no load current). Normal operation mode for good battery protection. 

2. Voltage controlled: Disconnect at 11.0 V fixed setting. Appropriate if bypass loads 

draw current directly from the battery. 

The controller is preset to Mode 1 from the factory. Changing the mode setting is 
described below. 
In case of doubts which mode to choose, consult your dealer because this has to be 
evaluated depending on the battery used. 

Settings 

The controller can be configured for special operation. For this purpose, open the 

cover of the controller by removing the screws on the back side. 

WARNING: The controller should not be opened while connected and in opera-
tion! 

When the controller is opened, there are 3 jumpers on the electronic board: 

 

For changing, put the jumper either on 
both contact pins or only on one 
contact pin: 
 

Closed jumper 

1

3

2

Open  
jumper 

With these jumpers, the following settings can be configured: 

Jumper 

GEL (1) 

LVD (2) 

BUZ (3) 

Function 

Battery type  

Function of low voltage 
disconnect 

Acoustic alarm signal 

Setting jumper 
open 

Liquid  
electrolyte  

State of charge con-
trolled 

Alarm off 

Setting jumper 
closed 

GEL (VRLA 
battery) 

Voltage controlled 

Alarm on 

Factory setting 

Jumper open 

(liquid electro-
lyte) 

Jumper open state-of-

charge controlled 

Jumper closed 
Alarm on 

After completing the setting, replace the cover and tighten it with the screws. 

Safety Features 

The controller is protected against wrong installation or use: 

 

At the solar termi-

nal 

At the battery 

terminal 

At the load terminal

Battery connected 
with correct polarity 

Unrestricted Normal 

operation 

Unrestricted 

Battery connected 

with wrong polarity  Unrestricted 

Unrestricted. Acous-

tic Warning

Unrestricted 

Reverse polarity 

Yes, not at 24V 

system voltage. 

Yes, if only the 

battery is connected. 
Acoustic Warning 

Load output is 

protected. Loads 
might be damaged. 

Short circuit 

Unrestricted 

Unrestricted. 

CAUTION

: Battery 

must be protected 

by fuse. 

Unrestricted 

Overcurrent No 

protection 

----------------------- 

Controller switches 
off load terminal. 

Thermal overload  No protection 

-----------------------  Controller switches 

off load terminal. 

No connection 

Unrestricted 

Unrestricted 

Unrestricted 

Reverse Current 

Unrestricted 

----------------------- 

----------------------- 

Overvoltage 

Varistor 56 V, 2,3 J  Max. 40 V 

Controller switches 

off load terminal. 

Undervoltage Normal 

operation 

Controller switches 
off load terminal. 

Controller switches 
off load terminal. 

WARNING: The combination of different error conditions may cause damage to 
the controller. Always remove the error before you continue connecting the 

controller! 

Error Description 

Error Display 

 

Reason 

Remedy 

Battery is low 

Load will reconnect as 
soon as battery is 
recharged. 

Overcurrent/ Short 
circuit of loads 

Switch off all loads. 
Remove short circuit. 

Controller will switch 
on load automatically 
after max 1 minute. 

Battery voltage too 
high (>15.5 / 31.0 V) 

Check if other sources 
overcharge the battery. 

If not, controller is 
damaged. 

Loads are not 
supplied 

Battery wires or 

battery fuse damaged, 
battery has high 

resistance 

Check battery wires, 

fuses and battery. 

Battery is empty 
after a short 

time 

Battery has low 
capacity 

Change battery 

Battery is not 
being charged 

during the day 

Solar array faulty or 
wrong polarity 

Remove faulty connec-
tion/reverse polarity  

 

Battery wrong 

polarity 

Permanent 

sound 

Battery is connected 

with reverse polarity 

Remove reverse 

polarity 

General Safety and Usage Recommendations 

Intended Use 

The charge controller is intended exclusively for use in photovoltaic systems with 12 V 

or 24 V nominal voltage and in conjunction with vented or sealed (VRLA) lead acid 
batteries only. 

Safety Recommendations 

Batteries store a large amount of energy. Never short circuit a battery under all 

circumstances. We recommend connecting a fuse (slow acting type, according to 
the nominal controller current) directly to the battery terminal. 
Batteries can produce flammable gases. Avoid making sparks, using fire or any naked 
flame. Make sure that the battery room is ventilated.  
Avoid touching or short circuiting wires or terminals. Be aware that the voltages on 
specific terminals or wires can be up to double the battery voltage. Use isolated 
tools, stand on dry ground and keep your hands dry. 
Keep children away from batteries and the charge controller. 
Please observe the safety recommendations of the battery manufacturer. If in 
doubt, consult your dealer or installer. 

Liability Exclusion 

The manufacturer shall not be liable for damages, especially on the battery, caused by 
use other than as intended or as mentioned in this manual or if the recommendations 
of the battery manufacturer are neglected. The manufacturer shall not be liable if 

there has been service or repair carried out by any unauthorized person, unusual use, 
wrong installation, or bad system design. 
 

Technical Data 

Nominal voltage 

12 / 24 V, automatic recognition 

Boost voltage 

14.5 / 29.0 V (25°C), 2 h  

Equalization voltage 

14.8 / 29.6 V (25°C), 2 h  

Float voltage 

13.7 / 27.4 V (25°C) 

Low Voltage Disconnect 
Function 

11.4-11.9 / 22.8-23.8 V controlled by state of charge 
11.0 / 22.0 V controlled by voltage 

Load reconnect voltage 

12.8 / 25.6 V 

Temperature compensa-
tion 

-4 mV/cell*K 

Max. solar panel current 

5 / 8 / 10 / 15 / 20 A according to model number @ 
50°C  

Max. load current 

5 / 8 / 10 / 15 / 20 A according to model number @ 

50°C  

Dimensions 

80 x 100 x 32 mm (w x h x d) 

Weight 180 

gr 

Max. wire size 

16 mm² (AWG #6) 

Self consumption 

4 mA 

Ambient temperature 

range 

-25 to + 50 °C 

Case protection 

IP 20 

Subject to change without notice. Version: CML041214 
Made in one of the following countries: Germany – China – Bolivia - India 
Phocos AG – Germany     www.phocos.com 

Summary of Contents for CML05-2

Page 1: ...rschnitte CML05 mind 2 5 mm CLM08 mind 4 mm CML10 mind 6 mm CML15 CML20 mind 10 mm HINWEIS Die Plus und Minus Leitung zum Solargenerator m ssen dicht nebeneinan der liegen um elektromagnetische Effekt...

Page 2: ...st tiefentladen Last schaltet automatisch zu wenn die Batterie nachgeladen wurde berstrom Kurzschluss Verbraucher Alle Verbraucher abschalten berstrom Kurzschluss beseitigen Regler schaltet nach ca 1...

Page 3: ...r array Mind the recommended wire size CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm REMARK Place positive and negative wire close to each other to minimize electro magnetic eff...

Page 4: ...r Display Reason Remedy Battery is low Load will reconnect as soon as battery is recharged Overcurrent Short circuit of loads Switch off all loads Remove short circuit Controller will switch on load a...

Page 5: ...ndado CML05 m n 2 5 mm CLM08 m n 4 mm CML10 m n 6 mm CML15 CML20 m n 10 mm OBSERVACI N para minimizar los efectos electromagn ticos coloque el cable positivo al lado del cable negativo OBSERVACI N Los...

Page 6: ...te Cortocircuito de consumos Desconectar todos los consumos Suprimir cortocircuito El controlador activar autom ticamente el consumo despu s de 1 minuto como m ximo El voltaje de la bater a es demasia...

Page 7: ...lle des c bles CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm REMARQUE placez le c ble positif et le c ble n gatif pr s l un de l autre afin de minimiser les effets lectromagn ti...

Page 8: ...cuit de charges Eteindre toutes les charges D brancher le court circuit Le contr leur allumera le r gulateur de charge automatiquement apr s 1 minute au maxi mum Tension de la batterie trop lev e 15 5...

Page 9: ...5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm OPMERKING plaats de positieve en negatieve kabel dicht naast elkaar om de kans op elektromagnetische effecten te verkleinen OPMERKING zonnepane...

Page 10: ...neer de accu weer voldoende is opgeladen Overstroom kortsluiting aangesloten apparatuur Alle aangesloten apparatuur uitschakelen Kortsluiting opheffen Regelaar schakelt last automatisch in na max 1 mi...

Page 11: ...Observe o tamanho do fio recomendado CML05 m n 2 5 mm CML08 m n 4 mm CML10 m n 6 mm CML15 CML20 m n 10 mm OBS coloque os fios positivo e negativo pr ximos um ao outro para minimizar efeitos electromag...

Page 12: ...o Erro Mostrador Raz o Solu o Bateria est com carga baixa Carga ser reconectada assim que a bateria for recarregada Sobreintensidade Curto circuito dos dispositivos Desligue todos os dispositivos Remo...

Page 13: ...solare Attenetevi alla grandezza del cavo raccomandata CML05 min 2 5 mm CLM08 min 4 mm CML10 min 6 mm CML15 CML20 min 10 mm NOTA mettete il cavo positivo e quello negativo vicini l uno all altro per...

Page 14: ...tutti i carichi Rimuovere cortocircuito Il regolatore accender il carico automaticamente al massimo dopo 1 minuto Tensione batteria troppo alta 15 5 31 0 V Controllate se altre fonti sovraccaricano l...

Reviews: