40
Display
Battery is low
Load will reconnect
as soon as battery is
recharged.
Overcurrent /
Short circuit of
loads
Switch off all loads.
Remove short circuit.
Controller will switch
on load automatically
after max 1 minute.
Controller is
thermally
overloaded and has
disconnected the
loads.
Battery wires or
battery fuse
damaged, battery
has high resistance
Check battery
wires, fuses and
battery.
Error Description
Loads are not
supplied
Error condition
Reason
Remedy
Battery voltage
too high
(>15.5 / 31.0 V)
Check proper
ventilation of
controller.
After cooling down the
loads are reconnected
automatically.
Check if other sources
overcharge the battery.
If not, controller is
damaged.