TESTING
24hrs Initial charge time required.
The emergency lighting must be inspected and tested regularly in accordance
with local codes of practice:
note:
for safety reasons tests should be carried out during daylight hours.
AFTER INSTALLATION
Allow 24 hours to ensure full battery charge and then interrupt the supply; the
maximum duration time is 3 hours check that LEDs are still lighting.
FUNCTIONAL TEST (Short)
Monthly, a short press on the test button (5s) serves to check the functionality of
the emergency unit, the batteries and LED module.
DURATION TEST
Full duration test should be carried out annually, interrupt mains and check LED
lights. LEDs will light and should last for a minimum 3 hours operation:
batteries must be replaced when they can no longer support 3 hour operation.
INSTALLATION MAINTENANCE RECORD
Month
TEST
Year 1
Year 2
Year 3
Year 4
(Out of Warranty)
Signed
Date
Signed
Date
Signed
Date
Signed
Date
1
Short
2
Short
3
Short
4
Short
5
Short
6
Short
7
Short
8
Short
9
Short
10
Short
11
Short
12
Short
3 Hr
Installer
Installation Date
Installation Test Date
LED
STATUS
COMMENT
Green
Standby, system ok
Mains operation, battery charging
Off
Battery Operation
Emergency mode:
Mains disconnected or Mains failure
INDICATOR LED
System status is shown locally by the indicator LED.