CAPAROC system
32 / 66
PHOENIX CONTACT
109745_en_01
6.1.2
Programming (2-channel circuit breakers)
•
Switch the channel on by pressing the corresponding LED button.
•
Set the necessary nominal current via the rotary switch. The channel LED starts to flash
green.
•
Press the channel LED button for >2 seconds to save the new current value.
Note: Initial programming
After the channel has been switched on, the channel may switch off and the LED may
flash red.
–
Set the nominal current via the rotary switch while it is switched off. The LED now
flashes red/green.
–
Press the channel LED button for >2 seconds to save the new current value.
Nominal current assistant
•
Program the channel to the highest value (e.g., 10 A).
•
Start up the system so that the operating current flows.
•
Turn the rotary switch down step-by-step so that it approaches the operating current
that is currently flowing. This will enable you to find the appropriate setting for the chan
-
nel. The channel LED flashes green in the process. If the channel LED changes and
starts to flash yellow/green, the selected setting is too low for the system current that is
currently flowing.
•
Turn the rotary switch back up one position.
•
Press the channel LED button for >2 seconds to save the new current value.
Red
On
Channel switched off, overload or short-circuit trip
-
ping, 5-second cool-down phase.
It is not possible to switch the channel on while the
LED is illuminated.
Flashing
Channel switched off, overload or short-circuit trip
-
ping.
Switch the channel back on by pressing the corre
-
sponding LED button.
Red/yellow
Flashing
Channel is in overload mode and will be switched off
in approx. 5 seconds.
Check the configuration.
Table 6
-
1
1- and 4-channel visual signaling
Signaling (LED)
Description
Summary of Contents for 1110984
Page 1: ...User manual CAPAROC System and installation...
Page 20: ...CAPAROC system 20 66 PHOENIX CONTACT 109745_en_01...
Page 22: ...CAPAROC system 22 66 PHOENIX CONTACT 109745_en_01...
Page 28: ...CAPAROC system 28 66 PHOENIX CONTACT 109745_en_01...
Page 52: ...CAPAROC system 52 66 PHOENIX CONTACT 109745_en_01...
Page 54: ...CAPAROC system 54 66 PHOENIX CONTACT 109745_en_01 Figure 8 1 PC WORX FIRMWARE UPDATER...
Page 67: ......