CAPAROC system
34 / 66
PHOENIX CONTACT
109745_en_01
6.2
Connecting loads
Switching off the channel
Before connecting the load, make sure that the relevant channel on which the load is to be
operated is switched off (LED is off).
Connecting the load
Connect the load via the load output of the relevant circuit breaker module as described in
Section 5, “Connecting or removing cables”
.
Switching on the channel
Then start the channel up again by pressing the channel LED (green LED).
6.3
Diagnostic and status indicators
6.3.1
Indicators on the power module
The power modules have status LEDs to indicate the current operating state.
Table 6
-
3
Visual signaling of the PROFINET power module (PM PN)
LED
Description
Designation
Color
Meaning
State
PWR
Green/yel
-
low/red
Voltage indicator
Green on
Operating voltage present
Red on
Operating voltage outside the nominal voltage
range
Flashing
yellow
Firmware update is in progress
Off
Operating voltage not present
BF
Red
Bus error
On
No bus connection
Flashing
Bus connection present, no connection to a
PROFINET controller
SF
Red
System error
On
PROFINET diagnostic data available
RDY
Green
Ready
On
Device is ready for operation
Off
Device is not ready for operation
Table 6
-
4
Visual signaling of the power module status-reset (PM S-R)
LED
Description
Designation
Color
Meaning
State
PWR
Green/yel
-
low/red
Voltage indicator
Green on
Operating voltage present
Red on
Operating voltage outside the nominal voltage
range
Off
Operating voltage not present
Summary of Contents for 1110984
Page 1: ...User manual CAPAROC System and installation...
Page 20: ...CAPAROC system 20 66 PHOENIX CONTACT 109745_en_01...
Page 22: ...CAPAROC system 22 66 PHOENIX CONTACT 109745_en_01...
Page 28: ...CAPAROC system 28 66 PHOENIX CONTACT 109745_en_01...
Page 52: ...CAPAROC system 52 66 PHOENIX CONTACT 109745_en_01...
Page 54: ...CAPAROC system 54 66 PHOENIX CONTACT 109745_en_01 Figure 8 1 PC WORX FIRMWARE UPDATER...
Page 67: ......