Process, parameter, and diagnostic data
109745_en_01
PHOENIX CONTACT
43 / 66
6
Byte
0
Switching status, channel 3
0 = channel is switched off
1 = channel is switched on
1
Warning 80% I
Nom
, channel 3
0 = warning inactive
1 = warning active
2
Overload, channel 3
0 = no error
1 = overload shutdown
3
Short circuit, channel 3
0 = no error
1 = short-circuit shutdown
4
Defect, channel 3
0 = no defect
1 = hardware is defective
5 ... 7
Reserved
0
7
Byte
0 ... 7
Set nominal current, channel 3
{1 ... 10} A
8
Byte
0 ... 7
Flowing current, channel 3
0 ... 255 (
=
0 ... 25.5 A)
9
Byte
0
Switching status, channel 4
0 = channel is switched off
1 = channel is switched on
1
Warning 80% I
Nom
, channel 4
0 = warning inactive
1 = warning active
2
Overload, channel 4
0 = no error
1 = overload shutdown
3
Short circuit, channel 4
0 = no error
1 = short-circuit shutdown
4
Defect, channel 4
0 = no defect
1 = hardware is defective
5 ... 7
Reserved
0
10
Byte
0 ... 7
Set nominal current, channel 4
{1 ... 10} A
11
Byte
0 ... 7
Flowing current, channel 4
0 ... 255 (
=
0 ... 25.5 A)
Table 7
-
7
Input process data of CAPAROC E4 12-24DC/1-10A
Byte
offset
Data
type
Bit
Description
Value range
Summary of Contents for 1110984
Page 1: ...User manual CAPAROC System and installation...
Page 20: ...CAPAROC system 20 66 PHOENIX CONTACT 109745_en_01...
Page 22: ...CAPAROC system 22 66 PHOENIX CONTACT 109745_en_01...
Page 28: ...CAPAROC system 28 66 PHOENIX CONTACT 109745_en_01...
Page 52: ...CAPAROC system 52 66 PHOENIX CONTACT 109745_en_01...
Page 54: ...CAPAROC system 54 66 PHOENIX CONTACT 109745_en_01 Figure 8 1 PC WORX FIRMWARE UPDATER...
Page 67: ......