Installation and Commissioning
107460_en_00
PHOENIX CONTACT
27
2.3.2
Grounding
The grounding is performed with a slip-on sleeve (noiseless ground / functional earth
ground).
1.
Strip approx. 5 mm (0.197") off the wires.
2.
Fit the stripped wires with a slip-on sleeve.
3.
Plug the slip-on sleeve on the flat tab.
Figure 2-18
Noiseless ground
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The conductor
must have a minimum cross-section of 1.5 mm² (16 AWG) and must be kept as short as
possible.