Installation and Commissioning
107460_en_00
PHOENIX CONTACT
9
2
Installation and Commissioning
2.1
Unpacking the Device
Unpack all parts carefully and check the contents for any visible damage in transit. Also
check whether the shipment matches the specifications on your delivery note.
If you notice damages in transit or discrepancies, please contact us immediately.
2.2
Mounting the Device
The device can be easily and quickly mounted from the rear of the device. A panel thickness
of 1 mm to 6 mm (0.039" to 0.236") is permitted for proper mounting.
1.
Cut the mounting cutout in the housing for the device size to be installed.
2.
Push the device through the mounting cutout from the front.
Figure 2-1
Mounting the device using a mounting bracket
NOTICE: Damage
When installing the device, leave a gap of at least 30 mm (1.181") around the device to
ensure sufficient air circulation.
NOTICE: Damage
When the operating device is installed horizontally, please note that additional sources of
heat beneath the operating device may result in heat accumulation.
Make sure to allow sufficient heat dissipation!
Please observe the permissible temperature range specified in the technical data when
operating the device.
NOTICE: Damage
In order to ensure the degree of protection specified in the technical data, observe the fol-
lowing points:
–
A tolerance of ±0.5 mm is maintained for the mounting cutout.
–
The seal lies flat against the mounting surface.
–
The number of mounting brackets, given in the technical data, is used.
–
The threaded pins of the mounting brackets are tightened uniformly to a maximum
torque of 1 Nm.