Shielding
Shielding is used to reduce the effects of interference on the system. In the Inline system,
remote bus cables and the cables to connect terminals for analog signals are shielded.
Observe the following points when installing shielding:
–
Connect the shielding via the shield connector. Fasten the shielding so that as much of
the braided shield as possible is held underneath the clamp of the shield connection.
–
Make sure there is good contact between the connector and base.
–
Do not damage or squeeze the wires. Do not strip more than 8 mm off the wires.
–
Always connect analog sensors and actuators with shielded, twisted pair cables.
Connecting the remote
bus cable
The remote bus cable is shielded. It is connected using the shield connector.
Connecting sensors and
actuators
Sensors and actuators are connected using the Inline connectors. Each terminal-specific
data sheet indicates which connector(s) can be used for which terminal.
Please refer to Section “Terminal point assignment” on page 18 for the assignment of the
terminal points.
In order to improve noise immunity, Phoenix Contact recommends a 3-wire, shielded
cable.