Commissioning and functional test
5981_en_06
PHOENIX CONTACT
59
The errors have the following priority:
–
An error on the local station has a higher priority than an error on the opposite station.
–
A bus error has a higher priority than a configuration error.
Example:
One station is operating correctly, the other station is faulty and has an illegal
configuration. The faulty bus must be repaired before the field multiplexer stations can
display the configuration error.
4)
●
●
●
●
○
(Same as 3) and local bus not operable
–
See 3)
–
Check correct position of the terminals
–
Check local bus supply
5)
●
●
●
●
●
(Same as 3) and local bus configuration
not permitted
–
See 3)
–
Check local bus configuration
(are all the terminals permitted, and is
the arrangement complementary?), see
6)
●
●
⊙
○
○
Different firmware versions on the field
multiplexer stations
–
Only use field multiplexers with the same
firmware in the system
–
Replace the field multiplexer
–
Send field multiplexer for service
7)
●
●
○
●
○
Local bus not operable (bus error)
–
Check correct position of the terminals
–
Check local bus supply
–
Check the LEDs on the devices (D LED
flashing?), see terminal-specific data
sheets or Section “Localizing errors on a
field multiplexer station” on page 60
8)
●
●
○
●
●
Local bus configuration not permitted
Check local bus configuration, see page 43
9)
●
●
○
⊙
○
Local bus of the opposite station not oper-
able
–
Check correct position of the terminals
–
Check local bus supply of the opposite
station
–
Check the LEDs on the devices (D LED
flashing?), see terminal-specific data
sheets or Section “Localizing errors on a
field multiplexer station” on page 60
10)
●
●
○
⊙
⊙
Local bus configuration of the opposite
station not permitted
–
Check local bus configuration of the
opposite station, see page 43
11)
●
●
○
○
●
The local bus configurations of the two
stations do not correspond
–
Check local bus configurations of the
both stations, see page 43
12)
●
○
○
●
○
I/O error on the local station
–
Check I/O supply of the local station
13)
●
○
○
⊙
○
I/O error on the opposite station
–
Check I/O supply of the opposite station
14)
●
○
○
○
○
Field multiplexer system operating
–
Table 8-3
Possible LED combinations
No.
UL
ST
RE
LE
CE
Error
Remedy
ACHTUNG: Malfunction
Changes to a local bus configuration during operation are not permitted
under any
circumstances
. Always
switch off power
first before you make any changes to the field
multiplexer system.
Summary of Contents for 2861205
Page 1: ...User manual Configuring and installing the Inline field multiplexer...
Page 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...
Page 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...
Page 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...
Page 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...