Commissioning and functional test
5981_en_06
PHOENIX CONTACT
61
Example
Figure 8-2
Station with example diagnostic indicators (states A to C)
Figure 8-2 shows a station with two example error states. It shows that an I/O error has been
detected at terminal 5 or that terminal 4 has failed and shows the behavior of the diagnostic
indicators on the adjacent terminals.
Peripheral fault
Bus error
Figure 8-2 Example A:
No error
Figure 8-2 Example B:
Peripheral fault
Figure 8-2 Example C:
Bus error
LED on or flashing at 0.5 Hz/2 Hz/4 Hz
(on / slow / medium / fast)
5 9 8 1 A 0 0 6
S T
C E
U L
R E
L E
U S
U M
M U X
1
2
D
D O 2
1
2
D
D I 2
1
2
3
4
5
D
A I 2
1
2
3
4
D
D I 4
B
C
A
Error:
Short circuit at terminal 4 (IB IL 24 DO 2-2A)
Effect:
field multiplexer:
UL
LED and
LE
LED are on (see Table 8-3, no. 12)
Opposite station:
UL
LED is on,
LE
LED is flashing (see Table 8-3, no. 13)
Terminal 4:
D
LED flashes at 2 Hz
Other terminals:
Remain unchanged
Alarm relay:
Not activated
Error:
Local bus has been interrupted after terminal 3 and before terminal 4
Effect:
field multiplexer:
UL
,
ST
and
LE
LEDs are on (see Table 8-3, no. 7)
Opposite station:
UL
and
ST
LEDs are on,
LE
LED is flashing (see Table 8-3, no. 7)
Terminal 4:
D
LED flashing at 4 Hz (bus error)
Other terminals:
D
LEDs on all other terminals flashing at 0.5 Hz *)
Alarm relay:
Activated
*)
If the bus error is located on the forward path of the local bus, the devices before the
fault location flash at 0.5 Hz. If the error is located on the return path, irregular flash-
ing (switching off for short periods) can be observed on the LEDs of the devices be-
fore the fault location.
Summary of Contents for 2861205
Page 1: ...User manual Configuring and installing the Inline field multiplexer...
Page 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...
Page 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...
Page 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...
Page 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...