5981_en_06
PHOENIX CONTACT
71
A 2.5
Connecting the cables
Phoenix Contact offers a pre-assembled adapter cable as an optional accessory for the
connection from the PSI-MOS-RS485W2/FO... converter to the IB IL 24 MUX MA-PAC:
IB IL MUX-CAB PSI.
Figure A-2
IB IL MUX-CAB PSI cable
Table A-5
Connection between converter and field multiplexer
Converter
PSI-MOS-RS485W2/FO...
Field multiplexer
IB IL 24 MUX MA-PAC
Terminal point
Signal
Connector 1,
Terminal point
Signal
Color
5
Shield
1.4 / 2.4
Shield
–
6
GND
1.3
GND
Gray
7
Data positive D(B)
1.2
Data
Yellow
8
Data negative D(A)
2.2
/Data
Green
ACHTUNG: Malfunction
If you assemble the adapter cable for the connection between field multiplexer and
interface converter by yourself: Please make sure that the cable is not longer than 1 m.
5981A043
Summary of Contents for 2861205
Page 1: ...User manual Configuring and installing the Inline field multiplexer...
Page 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...
Page 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...
Page 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...
Page 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...