PSI-MOS-RS485W2/FO... fiber optic converters that can be
used
A 2.3
Basic field multiplexer settings
•
Set the same transmission mode (FO) on both field multiplexers.
To do so, insert
a jumper
from 1.1 to 2.1 (CONF
FO
) at connector 1 (see also Figure 7-3
•
Configure one field multiplexer station as master and the other one as slave (see
Section “Configuring the station as a master or a slave” on page 22).
The fiber optic converters are available for both glass fiber and for HCS fiber cables in
different performance classes. The appropriate ordering data can also be found in the
INTERFACE catalog from Phoenix Contact.
Table A-2
Fiber optic converters (with one fiber optic interface)
Order Designation
Order No.
Cable type used
Distance
PSI-MOS-RS485W2/FO 660 E
2708313
POF
Up to 100 m
HCS/PCF
Up to 800 m
PSI-MOS-RS485W2/FO 850 E
2708339
HCS/PCF
Up to 2800 m
Multi-mode glass fiber
Up to 4200 m
PSI-MOS-RS485W2/FO 1300 E
2708562
Multi-mode glass fiber
Up to 25 km
Single-mode glass fiber
Up to 45 km
Table A-3
Fiber optic converters (T coupler with two fiber optic interfaces)
Order Designation
Order No.
Cable type used
Distance
PSI-MOS-RS485W2/FO 660 T
2708300
POF
Up to 100 m
HCS/PCF
Up to 800 m
PSI-MOS-RS485W2/FO 850 T
2708326
HCS/PCF
Up to 2800 m
Multi-mode glass fiber
Up to 4200 m
You will find the additional terminal point assignment of the field multiplexer in Section
Summary of Contents for 2861205
Page 1: ...User manual Configuring and installing the Inline field multiplexer...
Page 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...
Page 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...
Page 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...
Page 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...