Basic field multiplexer settings
•
Configure one field multiplexer station as master and the other one as slave (see
Section “Configuring the station as a master or a slave” on page 22).
A 3.3
Configuring modems using software
First modem
No jumper must
be installed from 1.1 to 2.1 (CONF
FO
) on connector 1 of both field
multiplexers.
You will find the additional terminal point assignment of the field multiplexer in Section
“Terminal point assignment” on page 18.
•
Connect the modem and the PC via a serial 1:1 cable and
supply it with 24 V DC.
•
Start the PSI-MODEM-CONF configuration software on the
PC.
•
Select "Options, RS232" in the pulldown menu.
•
Select the COM port (e.g., COM1) in the "Serial Interface"
window.
•
Set the following parameters for the serial interface:
–
Baud rate: 9600 bps
–
Data bits: 8;
–
Parity: Even
–
Stop bits: 1
•
Store the settings with "OK".
•
Open a new configuration. To do so, select "File, New" in
the pulldown menu or click the "New" button.
It is not possible to edit the existing configuration.
Please create a new configuration.