QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
14 / 50
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Basic standard
Minimum normative
requirements of
EN 61000-6-5
Higher requirements in
practice (covered)
Pulse-shape magnetic field EN 61000-4-9
not required
1000 A/m
Comments
none
Criterion A
Damped oscillating magnetic field EN
61000-4-10
not required
100 kHz
110 A/m
not required
1 MHz
110 A/m
Comments
none
Criterion A
Attenuated sinusoidal oscillations (ring wave) EN 61000-4-12
Input
not required
2 kV (Test Level 4 -
symmetrical)
not required
4 kV (Test Level 4 -
asymmetrical)
Comments
none
Criterion A
Asymmetrical conducted disturbance variables EN 61000-4-16
Input, Output, Signals
15 Hz ... 150 Hz , 10 V on 1 V
150 Hz ... 1.5 kHz , 1 V
1.5 kHz ... 15 kHz , 1 V on 10 V
15 kHz ... 150 kHz , 10 V
( Test Level 3 )
15 Hz ... 150 Hz , 30 V on 3 V
150 Hz ... 1.5 kHz , 3 V
1.5 kHz ... 15 kHz , 3 V on 30 V
15 kHz ... 150 kHz , 30 V
( Test Level 4 )
50 Hz , 60 Hz , 10 V
(Permanent)
50 Hz , 60 Hz , 100 V
(1 s)
( Test Level 3 )
16.7 Hz , 50 Hz , 60 Hz , 30 V
(Permanent)
16.7 Hz , 50 Hz , 60 Hz , 300 V
(1 s)
( Test Level 4 )
Comments
Criterion A
Criterion A
Attenuated oscillating wave EN 61000-4-18
Input, Output
1 MHz , 1 kV
( Test Level 3 - symmetrical )
100 kHz , 1 MHz , 1 kV
( Test Level 3 - symmetrical )
10 MHz , 1 kV
1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
10 MHz , 1 kV
100 kHz , 1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
Signals
1 MHz , 1 kV
( Test Level 3 - symmetrical )
100 kHz , 1 MHz , 1 kV
( Test Level 3 - symmetrical )
1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
100 kHz , 1 MHz , 2.5 kV
( Test Level 3 - asymmetrical )
Comments
Criterion B
Criterion A