QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
29 / 50
10.3
FUSE MODE output characteristic curve
In the event of an overload (e.g.,
short circuit), the power
supply switches off the DC output permanently. The value of
the switch-off threshold and the time period for which it may
be exceeded can be freely selected. The power supply is
restarted via the remote contact. As an option, the power
supply can be switched on by switching the supply voltage
on the primary side off and on.
Selecting the FUSE MODE output characteristic curve sets
the following default values.
–
t
Fuse
= 100
ms
–
I
Fuse
= I
N
Figure 22
FUSE MODE output characteristic curve
t [s]
I
Out
[A]
I
Fuse
t
Fuse
0