QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
6 / 50
Input protection , AC ( to be connected externally upstream )
Input current I
In
Input protection
Circuit breaker
Neozed fuse
or equivalent
Power switch
Characteristics
A
B
C
D
K
gG
≤
13 x I
In
(maximum magnetic tripping)
4 A
-
-
-
6 A
-
-
8 A
-
-
10 A
-
13 A
-
16 A
Electric strength of the insulation
A
B
C
D
Type test (IEC/EN 60950-1)
2.5 kV AC
4 kV AC
0.5 kV DC
0.5 kV DC
Production test
2 kV AC
2 kV AC
0.5 kV DC
0.5 kV DC
Field test (with gas-filled surge arrester)
0.8 kV AC
1.1 kV DC
0.8 kV AC
1.1 kV DC
0.5 kV DC
0.5 kV DC
Field test (gas-filled surge arrester de-contacted)
2 kV AC
2.83 kV DC
2 kV AC
2.83 kV DC
0.5 kV DC
0.5 kV DC
Housing
Output
PE
Input
Signaling
C
A
B
D
B
L
N
(+)
(-)
+
POWER factor
0,4
0,5
0,6
0,7
0,8
0,9
1,0
I
[A]
Out
Power Factor
2
4
6
8
10
12
14
16
18
20
= U : 120 V AC/U
: 24 V DC
In
Out
= U : 230 V AC/U
: 24 V DC
In
Out