QUINT4-PS/1AC/24DC/40
108827_en_01
PHOENIX CONTACT
37 / 52
The cable lengths determined are based on the following parameters:
Maximum distance l [m] with circuit breaker Conductor cross section
A [mm²]
0.75
1.0
1.5
2.5
4.0
6.0
10.0
AWG
18
(17)
16
14
12
10
8
ABB S200
B6
10
13
20
33
53
80
133
B8
8
10
16
26
43
64
107
B10
6
8
12
21
34
51
85
B13
4
5
8
14
23
35
59
B16
3
4
6
10
16
24
41
B20
1
2
3
6
10
15
26
B25
1
1
2
4
6
10
17
C1
3
4
6
11
17
26
44
C1.6
7
10
15
25
41
62
103
C2
7
9
14
23
38
57
95
C3
8
10
16
26
42
64
107
C4
6
8
12
20
32
48
81
C6
4
5
8
14
23
34
57
C8
2
3
5
9
15
23
38
C10
1
2
3
6
9
14
24
C13
1
1
2
3
5
8
13
Z1
64
85
128
214
343
514
857
Z1.6
46
62
93
156
250
375
625
Z2
42
57
85
143
229
343
573
Z3
33
44
66
110
176
264
441
Z4
24
33
49
82
132
198
331
Z6
16
21
32
54
87
131
219
Z8
12
17
25
42
68
102
171
Z10
10
14
21
36
57
86
144
Z16
6
9
13
22
36
54
90
Tripping:
magnetic
DC correction factor (0 Hz):
Siemens = 1.4; ABB = 1.5
Characteristics:
A, B, C, Z
Characteristic A (3 times the rated current) x correction factor
Characteristic B (5 times the rated current) x correction factor
Characteristic C (10 times the rated current) x correction factor
Characteristic Z (3 times the rated current) x correction factor
Ambient temperature:
+20 °C
Internal resistance R
i
of the device circuit
breaker:
taken into consideration
Comments:
In addition to the short-circuit current, the power supply unit also supplies
half the nominal current for load paths connected in parallel.