Mounting and power supply
108147_en_00
PHOENIX CONTACT
4
Mounting and power supply
4.1
Mounting the device circuit breaker
Mounting location
The CBMC E4 ... IOL meets the IP20 degree of protection. The compact design means that
the device circuit breaker can be installed in standard terminal boxes.
Mounting/DIN rail
The device circuit breaker can be mounted tool-free on the DIN rail.
Removal
A standard tool (e.g., a bladed screwdriver with a blade width of 2.5 mm) can be used to re-
move the device circuit breaker.
Mounting position
Mount the device horizontally. The ventilation slots should be oriented upward or down-
ward. Maintain a minimum distance of 30 mm on the top and bottom to ensure convection
cooling (see Figure 4-1 "Convection cooling"and Figure 4-2 "Minimum distance").
Figure 4-1
Convection cooling
Figure 4-2
Minimum distance
CBMC
1
2 IN+
1
2
3
4
1
2
L+
L-
IN-
OUT+
1
2
3
4
IO-Link
C/Q
30
75
150
CBMC
1
2
3
4
1
2
L+
C/Q
1
2
IN+
IN-
OUT+
1
2
3
4
IO-Link
L-
Summary of Contents for CBMC E4 24DC/1-10A IOL
Page 1: ...User manual Multi channel electronic device circuit breaker with IO Link interface ...
Page 6: ...CBMC E4 IOL 6 44 PHOENIX CONTACT 108147_en_00 ...
Page 8: ...CBMC E4 IOL 8 44 PHOENIX CONTACT 108147_en_00 ...
Page 14: ...CBMC E4 IOL 14 44 PHOENIX CONTACT 108147_en_00 ...
Page 30: ...CBMC E4 IOL 30 44 PHOENIX CONTACT 108147_en_00 ...
Page 38: ...CBMC E4 IOL 38 44 PHOENIX CONTACT 108147_en_00 ...
Page 40: ...CBMC E4 IOL 40 44 PHOENIX CONTACT 108147_en_00 ...
Page 42: ...CBMC E4 IOL 42 44 PHOENIX CONTACT 108147_en_00 ...