Wireless LAN access points/Ethernet clients
7190_en_02
PHOENIX CONTACT
2-11
230 V AC
Figure 2-8
Connecting the 230 V supply
PoE
Supply the module from a suitable Power over Ethernet voltage source.
2.2.8.2
Connecting the network cable
Insert the network cable in the female connector labeled "HOST".
2.2.8.3
Grounding
All Factory Line devices must be grounded so that the data telegram is shielded from any
possible interference and this can be discharged to ground potential.
A conductor of at least 2.5 mm
2
must be used for grounding. Grounding can be provided in
the module wiring space via an eyelet ring that is screwed into the location indicated (see
Figure 2-7) or the metal surface to which the mounting plate is attached can be grounded.
2.2.8.4
Achieving IP65 protection
Place the supplied cable feed-throughs around all cables used (A). Select a suitable cavity
for the cable feed-through (B). All unused cavities must be sealed with filler plugs.
Figure 2-9
Fitting rubber grommets around the cables used
IP65 protection is achieved if:
The 230 V AC supply voltage is connected via the COMBICON connector provided
(MC 1.5/3-ST1F-5.08, Order No. 1900895).
719000017
X1: 24V/0V
DC
X2: L/PE/N
110V/230V AC
X3:
HOST
230 V AC
PE
A
B
24V/0V
DC
NOT USED
HOST
718900005