background image

IB IL 24/230 DOR 4/W-PC (-PAC)

6530B

11

Switching AC/DC Loads

Switching Large AC Loads

When switching large AC loads, the relay can be 
operated up to the corresponding maximum values for 
switching voltage, current, and power. The arc that 
occurs during shutdown depends on the current, 
voltage, and phase angle. This shutdown arc switches 
off automatically the next time the load current passes 
through zero.

In applications with an inductive load, an effective 
protective circuit must be provided, otherwise the life 
of the system will be reduced considerably.

To prolong the life of the IB IL 24/230 DOR 4/W-PC 
terminal as mush as possible when using lamp loads 
or capacitive loads, the current peak must not exceed 
6 A when the load is switched on.

Switching Large DC Loads

In DC operation, a relay can only switch a relatively 
low current compared with the maximum permissible 
alternating current. This maximum direct current value 
is also highly dependent on the voltage and is 
determined in part by design conditions, such as the 
contact distance and contact opening speed.

The corresponding current and voltage values are 
shown in Figure 9.

Figure 9

DC load limiting curve 
(REL-SNR-1XU/G 5 GOLD relay)

An unattenuated inductive load further reduces the 
values given here for switching currents. The energy 
stored in the inductivity can cause an arc to occur 
which forwards the current via the open contacts. 
Using an effective contact protective circuit in relay 
contacts with the same life enables you to switch 
currents that are virtually the same as with ohmic 
loads. 

Additional technical data is available on request.

I

Switching current in A

U

Switching voltage in V

Definition of the load limiting curve: For 1000 cycles, 
no constant arc should occur with a burning life 
> 10 ms.

If it is permitted to switch higher DC loads, 
several relay contacts can be switched 
in parallel.

1

1 0

1 0 0

1 0 0 0

V

U

I

0 . 1

1

1 0

5 6 6 3 A 0 1 3

A

Summary of Contents for IB IL 24/230 DOR 4/W-PC

Page 1: ...The IB IL 24 230 DOR 4 W PC and IB IL 24 230 DOR 4 W PC PAC only differ in the scope of supply see Ordering Data on page 17 Their function and technical data are identical For greater clarity the Orde...

Page 2: ...who are able to recognize and avoid any possible dangers Definitions for skilled workers according to EN 50110 1 1996 The instructions given in the IB IL SYS PRO UM E User Manual or the Inline System...

Page 3: ...the segment in which the terminal is located e g switching 230 V AC within a 24 V DC segment In this case place a distance terminal before and after the IB IL 24 230 DOR 4 W PC terminal see Ordering D...

Page 4: ...3 2 3 and 1 4 2 4 are jumpered It is therefore possible to transmit the power to supply several relays of IB IL 24 230 DOR 4 W PC terminals from one connector to the next via a jumper 1 2 1 2 3 4 1 2...

Page 5: ...conditioning LED Terminal point without metal contact Relay FE or PE depending on the area in which the terminal is used Electrically isolated area I O area including relay contact isolated from the l...

Page 6: ...ay contacts 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 D D O R 4 W 3 4 6 3 2 6 A 0 0 5 1 2 3 4 N C c o n t a c t M a i n c o n t a c t N O c o n t a c t N C c...

Page 7: ...4 1 6 3 2 6 A 0 0 6 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 D D O R 4 W 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 3 2 1 2 1 2 3 4 1 2...

Page 8: ...following protective circuits can be used Contact protective circuit Load protective circuit Combination of both protective circuits Figure 8 Contact protective circuit A load protective circuit B If...

Page 9: ...t o r H i g h d e l a y N o A d v a n t a g e s U n c r i t i c a l s i z i n g D i s a d v a n t a g e s A t t e n u a t i o n o n l y a b o v e U Z D Y e s A d v a n t a g e s C o s t e f f e c t i...

Page 10: ...i n a t i o n D i s a d v a n t a g e s E x a c t d i m e n s i o n r e q u i r e d H i g h i n r u s h c u r r e n t Capacitor C LLoad 4 RLoad 2 Resistor R 0 2 RLoad P r o t e c t i n g t h e l o a...

Page 11: ...missible alternating current This maximum direct current value is also highly dependent on the voltage and is determined in part by design conditions such as the contact distance and contact opening s...

Page 12: ...n data of other bus systems please refer to the appropriate electronic device data sheet GSD EDS Byte bit view Bit 0 3 0 2 0 1 0 0 Assignment Slot 4 3 2 1 N C contact 1 2 1 2 1 2 1 2 Main contact 1 3...

Page 13: ...t 70 kPa to 106 kPa up to 3000 m 9843 ft above sea level Degree of protection IP 20 according to IEC 60529 In the range from 25 C to 55 C 13 F to 131 F appropriate measures against increased humidity...

Page 14: ...lamp loads and capacitive loads 6 A for T 200 s Nominal power consumption of the coil at 20 C 68 F 330 mW from the 7 5 V supply Resistance of the coil at 20 C 68 F 119 12 Maximum switching frequency w...

Page 15: ...hing Voltage V DC Switching Current A 5 3 0 10 3 0 20 3 0 30 3 0 40 1 0 50 0 4 60 0 3 70 0 26 80 0 23 90 0 215 100 0 2 150 0 18 200 0 165 250 0 155 Load Current IL in A as a Function of the Switching...

Page 16: ...ssipation of the relay coil PL Power dissipation through the load current via the contacts IL Load current of the output Power Dissipation of the Housing Depending on the Ambient Temperature PHOU 2 7...

Page 17: ...connectors and labeling fields IB IL 24 230 DOR 4 W PC PAC 28 62 18 1 Terminal with four relay changeover contacts IB IL 24 230 DOR 4 W PC 28 60 41 3 Connector with seven terminals spring cage connect...

Page 18: ...x Contact 03 2003 Technical modifications reserved TNR 90 11 32 6 Phoenix Contact GmbH Co KG Flachsmarktstr 8 32825 Blomberg Germany 49 52 35 30 0 49 52 35 34 12 00 www phoenixcontact com Worldwide Lo...

Reviews: