IBS IL 24 BK-T/U

10/2001

Data Sheet 6291A

   

       

      

       

      

       

      

      

       

      

  

This data sheet is only valid in 
association with the "Configuring and 
Installing the INTERBUS Inline 
Product Range" User Manual 
IB IL SYS PRO UM E.

This bus terminal replaces the 
IBS IL 24 BK-T bus terminal, which 
was supplied until now (see page 7).

Function

The bus terminal connects an Inline station to the 
INTERBUS remote bus and provides the supply 
voltages for the connected devices.

Features

Remote bus connections using copper 
cables

Can supply an Inline station with all of the 
required 24 V voltages for low-level signals

Electrical isolation of the remote bus 
segments

Automatic configuration of the outgoing 
interface as remote bus interface or local bus 
interface

Support of up to 15 connected terminals with 
remote bus branch

Figure 1

IBS IL 24 BK-T/U terminal with 
connectors and end plate

Please note that the connectors are 
not supplied as standard with the 
terminal. To order these connectors, 
please refer to the "Ordering Data" on 
page 22.

The end plate is supplied with the bus terminal. 
Place this plate at the end of the Inline station. 
The end plate does not have any electrical 
function. It protects the station from ESD pulses 
and the user from dangerous voltage.

6 2 9 1 A 0 0 2

6 2 9 1 A 0 0 1

INTERBUS Inline Bus Terminal

Summary of Contents for IBS IL 24 BK-T/U

Page 1: ...V voltages for low level signals Electrical isolation of the remote bus segments Automatic configuration of the outgoing interface as remote bus interface or local bus interface Support of up to 15 co...

Page 2: ...A 0 0 3 B A R C B K T U R D L D U L U S U M Des Color Meaning BA Green Bus active RC Green Remote bus cable check RD Yellow Outgoing remote bus switched off LD Yellow Local bus switched off UL Green...

Page 3: ...1 DO1 Receive Green 2 1 DO1 Receive Yellow 1 2 DI1 Send Pink 2 2 DI1 Send Gray 1 3 F GND Reference potential Brown 2 3 Not used 1 4 2 4 Shield Shield potential is connected with a capacitor to functi...

Page 4: ...potential jumper and the FE spring on the bottom of the housing Functional earth ground is only used to discharge interference Connector 4 Power Connector 1 1 2 1 24 V DC US 24 V segment supply The su...

Page 5: ...may damage the terminal Observe the current carrying capacity The maximum total current of the potential jumpers UM and US is 8 A Ground the bus terminal Connect the bus terminal to functional earth...

Page 6: ...densation may appear on the outside of the housing if for example the terminal is brought into a closed room from a vehicle Permissible air pressure operation 80 kPa to 106 kPa up to 2000 m 6562 ft ab...

Page 7: ...fer depending on the individual module The permissible number of devices that can be connected depends on the specific station structure Functions Reconfiguration external If necessary you can connect...

Page 8: ...le when using two separate power supply units Behavior if voltage dips and interrupts occur Voltages main and segment supply that are transferred from the bus terminal to the potential jumpers follow...

Page 9: ...DC Tolerance 15 20 according to EN 61131 2 Ripple 5 Permissible range 19 2 V to 30 V Minimum current consumption at nominal voltage 0 10 A DC At no load operation i e incoming remote bus connected no...

Page 10: ...ns Power Interfaces Nominal value 2 x 5 V DC Tolerance 5 Ripple 1 5 Maximum output current 2 x 0 15 A DC Safety measures None Communications Power Internal Nominal value 1 x 5 V DC Tolerance 5 Ripple...