Error codes for F-Parameters
F-Parameters contain information to adapt the PROFIsafe layer to particular customer
specifications. Parameterization is also checked on a separate path of the PROFIsafe layer.
For Status-PDU diagnostics the following parameter errors can be distinguished in the
"PROFIsafe F-Parameter error" status type:
Table A-8
F-Parameter parameter errors
Error code
Error cause
Remedy
dec
hex
64
40
The parameterized F_Destination_Address does is not
match the PROFIsafe address set at the safety module
(F module).
Match the PROFIsafe address of the safety
module and the value in
F_Destination_Address.
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
Correct value.
68
44
Invalid parameterization of F_SIL.
The required SIL cannot be supported by the safety
module (F module).
Use device with the required SIL.
69
45
Invalid parameterization of F_CRC_Length.
The CRC length generated by the safety module (F
module) does not correspond to the required length.
Check device description.
70
46
Version of F-Parameter set invalid.
Version of the safety module (F module) does not match
the required version.
Check device description.
71
47
The checksum determined by the safety module (F
module) from the PROFIsafe parameters (CRC1) does
not match the CRC1 transmitted with the parameter
telegram.
Check F-Parameters, repeat calculation
Please refer to the corresponding data sheets or user manuals for detailed information on