IL PB BK DI8 DO4/EF-PAC
B-8
PHOENIX CONTACT
7725_en_01
B 2
Slot 1
On slot 1, indices are implemented with regard to the integrated DI8:
B 3
Slots 2 to 63
On slots 2-63, indices are implemented with regard to the I/O terminals that can be
connected:
Index 13:
PD IN
Function:
Input data of the integrated DI8
Access:
Read
Length:
1 byte
Index 13:
PD IN
Function:
Input data on the slot of connected terminals
Access:
Read
Length:
0 to 128 bytes
Index 47:
PCP access
Function:
Read and write PCP data on connected terminals via DP/V1
Access:
Read and write
Length:
Depends on the command and the PCP object
Structure:
See Section 3.4, page 3-4 and onwards.
Note:
During access via DP/V0, the PCP objects can be accessed directly, i.e.,
without being diverted via index 47.