32
5756B
9. Check the configuration.
10. Save the configuration on the parameterization memory.
11. Save the IBS CMD file on your local drive.
Once the configuration has been saved successfully on the
parameterization memory, reset the controller board with
IBS CMD or with a POWER-UP of the control system, in order
to check the proper execution of the saved configuration.
After successfully activating the stored configuration, the
controller board displays "RUN". If the configuration could not
be started, an appropriate error message appears on the
display (see back cover). When the INTERBUS system is
activated, the defined inputs and outputs of the controller
board become available. This completes the configuration
and startup of the INTERBUS system.
Save the configuration file on the parameterization
memory by activating write protection (slide switch on
the parameterization memory).
Starting the Entire System
To start the controller board in normal mode, POWER-UP the
control system. If installation has been completed correctly,
the INTERBUS system will start with the preset configuration.