7. Method of Operation
In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC
voltage without interruption at a load current up to 40 A. When the 24 V supply voltage is applied, the connected
battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output,
and the stored power ensures that all connected devices continue to operate without interruption. The professional
signaling via function LEDs and
fl
oating PDT contacts enables reliable evaluation of all the main operating states.
7.1. Output Voltage
In normal operation, the QUINT-DC-UPS output voltage corresponds to the usual supply voltage. If the supply
voltage drops more than 1 V in the space of 0.1 seconds or falls below the minimum threshold of 22 V, the device
switches to buffer mode.
If the output voltage drops below 20.4 V in buffer mode, this is indicated by the Alarm indicator.
If the output voltage drops to 19.2 V because the battery module is
fl
at, the device is shut down completely. When
the supply voltage is reapplied, the device automatically switches on again. The device is electronically
short-circuit-proof and idling-proof.
7.2. Signaling
Three
fl
oating PDT contacts and three indicators are provided for function monitoring.
xx - xx: Contact closed,
1x Alarm,
2x Battery Mode, 3x Battery Charge
x1 group contact,
x2 N/C contact, x3 N/O contact
7.3. Temperature Response
The charging rate of the connected battery module depends on the temperature.
7.4. Testing the Battery Module
A quality test is carried out on the battery module once a week and its presence is veri
fi
ed every minute.
A negative test result is indicated by the Alarm indicator.
Key/Indicators
Green
"“
Power IN OK
Yellow
!
Bat. Mode/Charge
Red
0
Alarm
Supply voltage OK,
battery module charging
ON
Flashing
OFF
Supply voltage OK,
battery module charged (normal operation)
ON
OFF
OFF
Buffer mode
OFF
ON
OFF
Battery module
fl
at
OFF
OFF
ON
- Battery module quality test negative
- No battery module
- Service
ON
OFF
ON
- Buffer time elapsed
- Remote shutdown activated
OFF
OFF
OFF
Key/Output
Bat. Charge
6
Bat. Mode
5
Alarm
4
Supply voltage OK,
battery module charging
31 - 33
21 - 22
Supply voltage OK,
battery module charged (normal operation)
31 - 32
21 - 22
Buffer mode
31 - 32
21 - 23
Battery module
fl
at
31 - 32
21 - 22
11 - 13
- Battery module quality test negative
- No battery module
- Service
31 - 32
21 - 22
11 - 13
- Buffer time elapsed
- Remote shutdown activated
21 - 22
11 - 13
Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40