PHOENIX CONTACT page 9  of  9

7. Method of Operation

In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC 

voltage without interruption at a load current up to 40 A. When the 24 V supply voltage is applied, the connected 
battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output, 
and the stored power ensures that all connected devices continue to operate without interruption. The professional 
signaling via function LEDs and 

fl

oating PDT contacts enables reliable evaluation of all the main operating states.

7.1. Output Voltage

In normal operation, the QUINT-DC-UPS output voltage corresponds to the usual supply voltage. If the supply 

voltage drops more than 1 V in the space of 0.1 seconds or falls below the minimum threshold of 22 V, the device 
switches to buffer mode.
If the output voltage drops below 20.4 V in buffer mode, this is indicated by the Alarm indicator.
If the output voltage drops to 19.2 V because the battery module is 

fl

at, the device is shut down completely. When 

the supply voltage is reapplied, the device automatically switches on again. The device is electronically 
short-circuit-proof and idling-proof.

7.2. Signaling

Three 

fl

oating PDT contacts and three indicators are provided for function monitoring.

 

xx - xx: Contact closed,  
1x Alarm,

2x Battery Mode,      3x Battery Charge  

x1 group contact,

x2 N/C contact,      x3 N/O contact

7.3. Temperature Response

The charging rate of the connected battery module depends on the temperature.

7.4. Testing the Battery Module

A quality test is carried out on the battery module once a week and its presence is veri

fi

ed every minute. 

A negative test result is indicated by the Alarm indicator.

Key/Indicators

Green 

"“

Power IN OK

Yellow 

!

Bat. Mode/Charge 

Red 

0

Alarm

Supply voltage OK,
battery module charging

ON

Flashing

OFF

Supply voltage OK,
battery module charged (normal operation)

ON

OFF

OFF

Buffer mode

OFF

ON

OFF

Battery module 

fl

at

OFF

OFF

ON

- Battery module quality test negative
- No battery module
- Service

ON

OFF

ON

- Buffer time elapsed
- Remote shutdown activated

OFF

OFF

OFF

Key/Output

Bat. Charge

6

Bat. Mode

5

Alarm

4

Supply voltage OK,
battery module charging

31 - 33

21 - 22

Supply voltage OK,
battery module charged (normal operation)

31 - 32

21 - 22

Buffer mode

31 - 32

21 - 23

Battery module 

fl

at

31 - 32

21 - 22

11 - 13

- Battery module quality test negative
- No battery module
- Service

31 - 32

21 - 22

11 - 13

- Buffer time elapsed
- Remote shutdown activated

21 - 22

11 - 13

Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40

 

PHOENIX CONTACT

05/01/05

TNR:101997-00-gb

http://www.phoenixcontact.com

Summary of Contents for QUINT-DC-UPS/24DC/40

Page 1: ...g is thus required for maximum system availability Three floating PDT contacts and three LEDs are provided for function monitoring which indicate all the operating states clearly So that relay signali...

Page 2: ...harge current Battery presence check time interval Battery quality test time interval Memory Medium Nominal voltage Nominal capacity Charge current QUINT DC UPS 24DC 40 DC UPS Module U u F Type Order...

Page 3: ...cations Signaling Power In OK Alarm Battery Mode Battery Charge Approvals Standards Electrical equipment of machines Electrical safety of IT equipment Industrial control equipment Shipbuilding Electro...

Page 4: ...ully The QUINT DC UPS is a built in device Installation and startup must only be carried out by qualified personnel The relevant country specific regulations e g VDE DIN must also be observed Before s...

Page 5: ...4 DC OK 24V 0 2A 11 21 12 13 2 11 Alarm Bat M ode Bat C harg e QUIN T D C U PS 24DC 20 Ord er No 28 66 23 9 Input Opera tional Voltage Output 24VDC 22A 22 5 3 0VDC 24VDC 20A APPROVALS Read in sta llat...

Page 6: ...onnected For reliable and safe to touch connections Strip 10 mm 0 39 in from the input and output side connector ends and 7 mm 0 28 in from the signal connector ends To maintain UL approvals use coppe...

Page 7: ...24DC type battery modules The following battery modules are recommended QUINT BAT 24DC 3 4AH Order No 2866349 QUINT BAT 24DC 7 2AH Order No 2866352 QUINT BAT 24DC 12AH Order No 2866365 When using QUIN...

Page 8: ...ce remains off until remote shutdown is deactivated Connected loads are supplied as long as the supply voltage is present 6 Setting Options on the Device Fig 13 6 1 Buffer Time Setting Buffer mode can...

Page 9: ...idling proof 7 2 Signaling Three floating PDT contacts and three indicators are provided for function monitoring xx xx Contact closed 1x Alarm 2x Battery Mode 3x Battery Charge x1 group contact x2 N C...

Reviews: