QUINT4-PS/1AC/24DC/1.3/PT
108338_en_00
PHOENIX CONTACT
9 / 28
Electromagnetic compatibility
CE basic standard
Minimum normative
requirements
Higher requirements in
practice (covered)
Conducted noise emission EN 55016
EN
61000-6-4 (Class A)
EN
61000-6-3 (Class B)
Noise emission EN 55016
EN
61000-6-4 (Class A)
EN
61000-6-3 (Class B)
Harmonic currents EN 61000-3-2
not required
0 kHz ... 2 kHz
Flicker EN 61000-3-3
not required
0 kHz ... 2 kHz
CE basic standard
Minimum normative
requirements of EN 61000-
6-2 (CE)
(immunity for industrial
environments)
Higher requirements in
practice (covered)
Electrostatic discharge EN 61000-4-2
Housing contact discharge
4 kV (Test Level 2)
8 kV (Test Level 4)
Housing air discharge
8 kV (Test Level 3)
8 kV (Test Level 3)
Comments
Criterion B
Criterion A
Electromagnetic HF field EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
80 MHz ... 1 GHz
Test field strength
10 V/m (Test Level 3)
20 V/m (Test Level 3)
Frequency range
1.4 GHz ... 2 GHz
1 GHz ... 6 GHz
Test field strength
3 V/m (Test Level 2)
10 V/m (Test Level 3)
Frequency range
2 GHz ... 2.7 GHz
Test field strength
1 V/m (Test Level 1)
Comments
Criterion B
Criterion A
Fast transients (burst) EN 61000-4-4
Input
2 kV (Test Level 3 -
asymmetrical)
4 kV (Test Level 4 -
asymmetrical)
Output
2 kV (Test Level 3 -
asymmetrical)
4 kV (Test Level X -
asymmetrical)
Signal
1 kV (Test Level 3 -
asymmetrical)
4 kV (Test Level X -
asymmetrical)
Comments
Criterion B
Criterion A
Surge current loads (surge) EN 61000-4-5
Input
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
2 kV (Test Level 4 -
symmetrical)
4 kV (Test Level 4 -
asymmetrical)
Output
0.5 kV (Test Level 2 -
symmetrical)
0.5 kV (Test Level 1 -
asymmetrical)
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)