Digital I/Os and diagnostic and status indicators
105752_en_03
PHOENIX CONTACT
45 / 56
Q3
ONBOARD_OUTPUT_BIT2 Flashes at 1 Hz (1 s clock)
Error when establishing the communication
(no connection)
Flashes at 2 Hz (500 ms clock) Error when sending or receiving data
Flashes at 4 Hz (250 ms clock) SafetyBridge communication breakdown
Flashes at 8 Hz (125 ms clock) “Manual” operating mode:
Manual acknowledgment via I7 required
“Automatic” operating mode:
Automatic acknowledgment
Message can be acknowledged via I7.
Q4
ONBOARD_OUTPUT_BIT3 Flashes at 1 Hz (1 s clock)
Bus length of the master does not match the
bus length of the slave.
Flashes at 4 Hz (250 ms clock) Bus configuration of the master does not
match the bus configuration of the slave.
Table A
-
3
Function description of the digital outputs
Output
Internal designation
Associated LED
Meaning
Table A
-
4
Function description of the digital inputs
Input
Internal designation
Function
Actuation
I1
ONBOARD_INPUT_BIT0
Configuration
0 = slave
1 = master
Via fixed wiring
I2
ONBOARD_INPUT_BIT1
Configuration of manual or au
-
tomatic acknowledgment of a
SafetyBridge communication
error;
TRUE = automatic,
FALSE = manual
Via fixed wiring
I5
ONBOARD_INPUT_BIT4
Selection for IP address set
-
tings
(0 = automatic/1 = manual)
Via fixed wiring
The I2 assignment must be set
identically for master and slave.
WARNING: Risk of injury due to unexpected machine start
-
up
Automatic acknowledgment of a SafetyBridge communication er
-
ror may cause an unexpected machine startup.
•
If you do not want the machine to start up/restart automatical
-
ly, configure the safety logic accordingly.